INSTALLING TRANSITION PIPE AND 
STARTER COLLAR
The transition pipe and starter collar shown 
in  Figure  9  are  supplied  with  the  fireplace, 
unattached  and  ready  for  installation.  Re-
move  starter  collar  and  set  aside.  Slide 
transition  pipe  over  vent  collar  and  attach 
with  a  minimum  of  three  screws.  Replace 
starter collar over transition pipe and attach 
using four screws located on leg stands (five 
used on model M42). To install B-vent piping, 
slide the first piece of B-vent over transition 
pipe and attach with either a minimum of two 
screws or other means approved by the vent 
manufacturer.
Figure 9 - Installing Transition Pipe and 
Starter Collar
B-Vent Piping
Transition Pipe
Starter Collar
Vent Collar
Pre-INstallatIoN PreParatIoN
Continued
VeNtING INstallatIoN
60° or greater. The total vertical height in this 
example represents the minimum height of 8 
feet and therefore the allowable lateral is 6 
feet when the 75% rule applies. If the lateral 
length  must  exceed  75%  then  the  system 
must be sized in accordance with Category I 
venting tables.
Example 2: Shows a multiple offset each at 
45° of inclination. Multiple offsets are permit-
ted if they do not exceed 45° of inclination. The 
total lengths of the two offsets are not required 
to meet the 75% allowable rule.
Example 3: Shows a single offset at 45° of 
inclination and therefore the lateral length at 
10 feet of offset does not have to meet the 
75% rule.
In each case the offsets must be supported 
and  firestops  must  be  positioned  wherever 
the vent must pass through a sub-floor, ceil-
ing joist or an attic overhang. The vent pipe 
must terminate vertically into a listed type vent 
cap  and  extend  a  sufficient  height  through 
an approved roof flashing, roof jack or a roof 
thimble. At all points listed clearances must 
be maintained.
Vent  terminations  must  be  located  in  ac-
cordance with height and proximity rules of 
NFPA No. 54. These rules apply to vents at 
12" diameter or less and require a minimum 
height in accordance with the roof pitch and a 
minimum of 8 ft. distance from a vertical wall 
or obstruction (see Figure 11, page 10).
A B-type venting system must be connected 
to the appliance for venting to the outside of 
the building.
The following section is provided as a guide 
to a standard B-type vent installation.
Standing codes requirements concerning B-
type vent installations may vary within your 
state,  province  or  local  codes  jurisdiction. 
Therefore, it is recommended that you check 
with  your  local  building  codes  for  specific 
requirements  or  in  absence  of  local  codes, 
follow Section 7.0 of the current National Fuel 
Gas Code ANSI Z223.1/NFPA 54
.
This  gas  appliance  must  be  vented  to  the 
outdoors only and may not be terminated into 
an attic space or into a chimney flue servicing 
a solid fuel burning appliance.
This  appliance  may  be  vented  through  a 
manufactured chimney system or a masonry 
chimney  using  a  B-vent  adapter  or  a  chim-
ney  liner  system  if  all  are  listed,  inspected 
and approved by local codes and/or building 
authorities.
The examples shown in Figure 10, page 10 
are  typical  of  most  B-vent  installations  and 
codes practices.
Example  1:  Shows  the  minimum  allowable 
system height and lateral offset for a 60° or 
greater inclination. Code specifies that offsets 
at  60°  or  greater  are  considered  horizontal 
and  must  follow  the  75%  rule  for  lateral  to 
total vertical system height. Codes also allow 
only  one  offset  in  the  total  system  when  at