Champion pp-3 Manuale Utente
C O N T R O L P A N E L S
The parameters that can be changed follow:
Temperature Units
This setting allows a different temperature unit to be used for display. You can switch
between Celsius and Fahrenheit.
between Celsius and Fahrenheit.
Parameter name: T E M P E R A T U R E U N I T S
Allowed values: C or F
Factory default: F
Allowed values: C or F
Factory default: F
Low Speed Frequency
This setting is used to set the frequency in the Omron Inverter Controller that controls the
low pump speed.
low pump speed.
Parameter name: P U M P L O W F R E Q U E N C Y
Allowed values: 0 to 1 0 0 Hertz
Factory default: 3 5
Allowed values: 0 to 1 0 0 Hertz
Factory default: 3 5
Medium Speed Frequency
This setting is used to set the frequency in the Omron Inverter Controller that controls the
medium pump speed.
medium pump speed.
Parameter name: P U M P M E D F R E Q U E N C Y
Allowed values: 0 to 1 0 0 Hertz
Factory default: 5 0
Allowed values: 0 to 1 0 0 Hertz
Factory default: 5 0
High Speed Frequency
This setting is used to set the frequency in the Omron Inverter Controller that controls the
high pump speed.
high pump speed.
Parameter name: P U M P H I G H F R E Q U E N C Y
Allowed values: 0 to 1 0 0 Hertz
Factory default: 6 8
Allowed values: 0 to 1 0 0 Hertz
Factory default: 6 8
Hold Pump Speed
This setting sets the pump speed for the Hold or Clean state.
Parameter name: H O L D P U M P S P E E D
Allowed values: L O W , M E D , H I G H
Factory default: L O W
Allowed values: L O W , M E D , H I G H
Factory default: L O W
38