The parameters that can be changed follow: 
Temperature Units 
This setting allows a different temperature unit to be used for display. You can switch 
between Celsius and Fahrenheit. 
Parameter name: T E M P E R A T U R E   U N I T S  
Allowed values:  C   or F  
Factory default: F  
 
Low Speed Frequency 
This setting is used to set the frequency in the Omron Inverter Controller that controls the 
low pump speed. 
Parameter name: P U M P   L O W   F R E Q U E N C Y  
Allowed values:  0  to 1 0 0  Hertz 
Factory default: 3 5  
Medium Speed Frequency 
This setting is used to set the frequency in the Omron Inverter Controller that controls the 
medium pump speed. 
Parameter name: P U M P   M E D   F R E Q U E N C Y  
Allowed values:  0  to 1 0 0  Hertz 
Factory default: 5 0  
High Speed Frequency 
This setting is used to set the frequency in the Omron Inverter Controller that controls the 
high pump speed. 
Parameter name: P U M P   H I G H   F R E Q U E N C Y  
Allowed values:  0  to 1 0 0  Hertz 
Factory default: 6 8  
 
Hold Pump Speed 
This setting sets the pump speed for the Hold or Clean state. 
Parameter name: H O L D   P U M P   S P E E D  
Allowed values: L O W ,   M E D ,   H I G H  
Factory default: L O W  