Tripp Lite 7.4kW Single-Phase Metered PDU, 230V Outlets (2-C19, 16-C13), IEC-309 230V 32A Blue, 12ft Cord, 2U Rack-Mount PDUMH32HV Manuale Utente
Codici prodotto
PDUMH32HV
SPECIFICATIONS
MODEL
NOMINAL
VOLTAGE
(50/60 HZ)
MAXIMUM
INPUT
CURRENT
METERED
OUTPUT
BANKS
AC INPUT
CONNECTOR
OUTLETS
(QUANTITY & TYPE)
RACK SPACE
3-PHASE SWITCHED PDU
s
(3-Phase Input, Single-Phase Output, Network-Grade Power Distribution, Load Meters, Network Interface and Remote Individual Outlet Control)
PDU3XVSR10G16
Input: 3-Phase 400V
Output: Single-Phase 230V
16A
3
IEC-309 Red 16A (
3P+N+E
)
(A)
(
3 m cord
)
24 (
21 C13+ 3 C19
)
0U (
178 cm long
)
(B, C)
PDU3XVSR3G16
Input: 3-Phase 400V
Output: Single-Phase 230V
16A
3
IEC-309 Red 16A (
3P+N+E
)
(A)
(
1 m cord
)
24 (
21 C13+ 3 C19
)
0U (
178 cm long
)
(B, C)
3-PHASE MONITORED PDU
s
(3-Phase Input, Single-Phase Output, Network-Grade Power Distribution, Load Meters and Network Interface)
PDU3XVN10G16
Input: 3-Phase 400V
Output: Single-Phase 230V
16A
3
IEC-309 Red 16A (
3P+N+E
)
(A)
(
3 m cord
)
36 (
30 C13 + 6 C19
)
0U (
178 cm long
)
(B, C)
PDU3XVN3G16
Input: 3-Phase 400V
Output: Single-Phase 230V
16A
3
IEC-309 Red 16A (
3P+N+E
)
(A)
(
1 m cord
)
36 (
30 C13 + 6 C19
)
0U (
178 cm long
)
(B, C)
SINGLE-PHASE SWITCHED PDU
s
(Network-Grade Power Distribution, Load Meters, Network Interface and Remote Outlet Control)
PDUMH15HVNET
220/230/240V
10A
1
C14 inlet
(D, E)
8
(C13)
1U
PDUMH20HVNET
220/230/240V
16A
1
C20 inlet
(D, F)
8
(C13)
1U
PDUMH20HVATNET
220/230/240V
16A
1
2 x C20 inlet
(D, G)
10
(8 C13 + 2 C19)
1U
PDUMH32HVNET
220/230/240V
32A
2
IEC-309 Blue 32A (
2P+E
)
(A)
16
(C13)
2U
PDUMV20HVNET
220/230/240V
16A
1
C20 inlet
(D)
24
(20 C13 + 4 C19)
0U
(163 cm long)
(B, C)
PDUMV32HVNET
220/230/240V
32A
2
IEC-309 Blue 32A (
2P+E
)
(A)
24
(20 C13 + 4 C19)
0U
(178 cm long)
(B, C)
SINGLE-PHASE MONITORED PDU
s
(Network-Grade Power Distribution, Load Meters and Network Interface)
PDUMNH20HV
220/230/240V
16A
1
C20 inlet
(D)
8
(C13)
1U
PDUMNH32HV
220/230/240V
32A
2
IEC-309 Blue 32A (
2P+E
)
(A)
16
(12 C13 + 4 C19)
2U
PDUMNV20HV
220/230/240V
16A
1
C20 inlet
(D, B)
24
(20 C13 + 4 C19)
0U
(163 cm long)
(B, C)
SINGLE-PHASE METERED PDU
s
(Network-Grade Power Distribution and Load Meters)
PDUMH20HV
220/230/240V
16A
1
C20 inlet
(D, F)
10
(8 C13 + 2 C19)
1U
PDUMH20HVAT
220/230/240V
16A
1
2 x C20 inlet
(D, G)
10
(8 C13 + 2 C19)
1U
PDUMH32HV
220/230/240V
32A
2
IEC-309 Blue 32A (
2P+E
)
(A)
18
(16 C13 + 2 C19)
2U
PDUMV20HV
220/230/240V
16A
1
C20 inlet
(D)
38
(32 C13 + 6 C19)
0U
(162 cm long)
(B, C)
SINGLE-PHASE BASIC PDU
s
(Network-Grade Power Distribution)
PDU12IEC
220/230/240V
16A
–
C20 inlet
(D)
14
(12 C13 + 2 C19)
1U or 0U
(44 cm long)
(B)
PDUNV
220/230/240V
16A
–
C20 inlet
(D, H)
14
(12 C13 + 2 C19)
1U or 0U
(44 cm long)
(B)
PDUH20DV
220/230/240V
16A
–
C20 inlet
(D, I)
14
(12 C13 + 2 C19)
1U or 0U
(44 cm long)
(B)
Certifications vary by model. (A) Splash-proof plug (IP44 protection rating). (B) 0U represents vertical rack installation. (C) PDU includes mounting buttons for toolless installation in compatible racks. Detachable 90° rotation
brackets allow PDU outlets to face the rear of the rack for improved access and airflow. (D) Connect each inlet to a user-supplied input power cord with a region-specific plug. Connect each plug to a compatible outlet.
(E) Includes detachable 198 cm input cord with C14 plug. (F) Includes detachable 259 cm input cord with C20 plug. (G) Includes primary and secondary AC inputs. The PDU automatically switches to the secondary input if the
primary input’s voltage or frequency deviates from the designated safe operating range. Also includes two 366 cm input cords with C20 plugs. (H) Includes 305 cm cord with C20 plug. (I) Includes 366 cm cord with C20 plug.
A
AC Outlets
B
AC Inlet (C14 or C20)
Connects to a user-supplied input power
cord with a region-specific plug.
cord with a region-specific plug.
C
Load Meter
Displays the connected equipment load
(current draw) in amps. 3-Phase models
include an advanced multimode load meter
that displays the PDU’s IP address,
the load for each bank/phase and
the load for each individual outlet.
(current draw) in amps. 3-Phase models
include an advanced multimode load meter
that displays the PDU’s IP address,
the load for each bank/phase and
the load for each individual outlet.
D
Network Interface
Enables PDU management over
Ethernet WAN, LAN or Internet via
SNMP, a standard Web browser, SSH
or telnet. Also supports remote
monitoring of temperature,
humidity and dry contacts via
ENVIROSENSE accessory, sold
separately.
Ethernet WAN, LAN or Internet via
SNMP, a standard Web browser, SSH
or telnet. Also supports remote
monitoring of temperature,
humidity and dry contacts via
ENVIROSENSE accessory, sold
separately.
E
Removable Mounting
Brackets
Support rackmount installation and surface mounting.
F
Circuit Breakers
Protect against short circuits
and overloads.
and overloads.
G
Toolless Mounting Buttons
Support toolless 0U (vertical)
installation in compatible
racks. Detachable 90° rotation
brackets allow PDU outlets to
face the rear of the rack for
improved access and airflow.
installation in compatible
racks. Detachable 90° rotation
brackets allow PDU outlets to
face the rear of the rack for
improved access and airflow.
H
Removable Cord Retention
Brackets
Secure and organize power
cords, reducing the risk of
accidental disconnection.
cords, reducing the risk of
accidental disconnection.
I
Metal Housing
Maximizes durability and safety.
J
Splash-Proof Plug
Splash-proof plug with IP44
protection rating connects to
a compatible outlet.
protection rating connects to
a compatible outlet.
K
Automatic Transfer Switch (ATS)
The PDU includes primary and secondary AC inputs, which
allows the PDU to automatically switch to the secondary
input if the primary input’s voltage or frequency deviates
from the designated safe operating range. ATS PDUs can
be used for power redundancy in single-cord devices or to
make any on-line UPS system hot-swappable. Note: If the
primary input is plugged into a UPS system, it must be an
on-line UPS system.
allows the PDU to automatically switch to the secondary
input if the primary input’s voltage or frequency deviates
from the designated safe operating range. ATS PDUs can
be used for power redundancy in single-cord devices or to
make any on-line UPS system hot-swappable. Note: If the
primary input is plugged into a UPS system, it must be an
on-line UPS system.
Switched Outlet
Cord Retention Bracket
Splash-Proof Plugs
Load Meter
Network Interface
ENVIROSENSE
Toolless Mounting Button