Installing the Second AC Power Supply Unit 
For redundancy, the SV Director Server requires two AC power supplies, 
enabling one to become a backup for the other in case of failure. Redundant 
power supplies also enable you to ―hot-swap‖ a power supply if you need to 
replace it. In other words, you can replace a power supply while the appliance is 
running. To maintain hot-swap capability, make sure that there is an active 
power supply in both appliance slots before replacing (hot-swapping) a power 
supply. 
The AC power supplies are accessible from the rear panel. When you unpack 
the Cisco ADE 2140 Series appliance, only one space in the power supply 
module is occupied. The empty space is occupied with a blank filler panel. 
Both power supplies for the SV Director Server must be AC. 
Warning!  Never install an AC power module and a DC power module in the 
same chassis. Statement 1050 
Figure 22.  Cisco ADE-2140 Server 
– Rear View with One  PSU 
 
 
Caution! Before replacing an existing power supply, you must first take the 
server out of service. To do so, turn off all external devices connected to the 
server, turn off the power button on the server, and unplug the AC power cord. 
To install the second power supply unit: 
1. 
Notice there is a single power supply on the far right of the box and a ―filler‖ 
unit immediately to its left.  
2.  Remove the blank filler panel from the rear panel by pressing the two release 
tabs (1) toward each other, as illustrated in Figure 23.  
Figure 23.  Blank Filler Panel and AC Power Module