Toshiba G3 TOSVERT-130 Manuale Utente

Pagina di 62
 
 32
(Note 3
If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is 
0.01.  If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier 
is 0.1.  These values are automatically set according to the inverter’s capacity. 
 
 
Table 4:  Output Terminal Status Monitor (register 0D) 
Lower 
Byte 
Bit Output 
Terminal 
Single-Bit 
Read Mask 
 
bit 0 
unused (always 0) 
 
 
 
 
bit 1 
unused (always 0) 
 
 
 
 bit 
FAN 
OFF 
ON 
0004 
 
bit 3 
FL 
FLB-FLC shorted 
FLA-FLC shorted 
0008 
 
bit 4 
MS relay 
OFF 
ON 
0010 
 
bit 5 
OUT (option) 
OUTB-OUTC shorted 
OUTA-OUTC shorted 
0020 
 
bit 6 
RCH 
RCHA-RCHC open 
RCHA-RCHC shorted 
0040 
 
bit 7 
LOW 
LOWA-LOWC open 
LOWA-LOWC shorted 
0080 
 
Table 5:  Inverter Status 1 (register 0E)
 
Lower 
Byte 
Bit Inverter 
Status 
Single-Bit 
Read Mask 
 
bit 0 
running (acc/dec) 
 
running 0001 
 
bit 1 
unused (always 0) 
 
 
 
 
bit 2 
forward / reverse 
reverse 
forward 
0004 
 
bit 3 
acc/dec #1/#2 
acc/dec #1 
acc/dec #2 
0008 
 
bit 4 
for inverter use 
 
 
 
 
bit 5 
for inverter use 
 
 
 
 
bit 6 
for inverter use 
 
 
 
 
bit 7 
jog/normal mode 
normal (acc/dec) 
jog mode 
0080 
 
Upper 
Byte 
Bit Inverter 
Status 
Single-Bit 
Read Mask 
 
bit 0 
feedback ON/OFF 
OFF 
feedback active 
0001 
 
bit 1 
DC inj. braking 
OFF 
DC inj. braking active 
0002 
 
bit 2 
V/F #1/#2 
V/F #1 
V/F #2 
0004 
 
bit 
coasting not 
coasting coasting 
0008 
 
bit 4 
emergency off 
not in emergency off 
in emergency off 
0010 
 
bit 5 
for inverter use 
 
 
 
 
bit 6 
for inverter use 
 
 
 
 
bit 7 
for inverter use 
 
 
 
 
Table 6 :  Inverter Status 2 (register 0F) 
Upper 
Byte 
Bit Inverter 
Status 
Single-Bit 
Read Mask 
 
bit 
accelerating not 
accelerating accelerating  0001 
 
bit 
decelerating not 
decelerating decelerating  0002 
 
bit 2 
for inverter use 
 
 
 
 bit 
retry 
not 
retrying 
retrying 
0008 
 
bit 4 
running (including DC 
injection braking) 
stopped running 
0010 
 
bit 5 
for inverter use 
 
 
 
 
bit 6 
for inverter use 
 
 
 
 
bit 
tripped not 
tripped tripped 
0080