Toshiba G3 TOSVERT-130 Manuale Utente
32
(Note 3)
If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier
is 0.1. These values are automatically set according to the inverter’s capacity.
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier
is 0.1. These values are automatically set according to the inverter’s capacity.
Table 4: Output Terminal Status Monitor (register 0D)
Lower
Byte
Bit Output
Terminal
0
1
Single-Bit
Read Mask
bit 0
unused (always 0)
bit 1
unused (always 0)
bit
2
FAN
OFF
ON
0004
bit 3
FL
FLB-FLC shorted
FLA-FLC shorted
0008
bit 4
MS relay
OFF
ON
0010
bit 5
OUT (option)
OUTB-OUTC shorted
OUTA-OUTC shorted
0020
bit 6
RCH
RCHA-RCHC open
RCHA-RCHC shorted
0040
bit 7
LOW
LOWA-LOWC open
LOWA-LOWC shorted
0080
Table 5: Inverter Status 1 (register 0E)
Lower
Byte
Bit Inverter
Status
0
1
Single-Bit
Read Mask
bit 0
running (acc/dec)
running 0001
bit 1
unused (always 0)
bit 2
forward / reverse
reverse
forward
0004
bit 3
acc/dec #1/#2
acc/dec #1
acc/dec #2
0008
bit 4
for inverter use
bit 5
for inverter use
bit 6
for inverter use
bit 7
jog/normal mode
normal (acc/dec)
jog mode
0080
Upper
Byte
Bit Inverter
Status
0
1
Single-Bit
Read Mask
bit 0
feedback ON/OFF
OFF
feedback active
0001
bit 1
DC inj. braking
OFF
DC inj. braking active
0002
bit 2
V/F #1/#2
V/F #1
V/F #2
0004
bit
3
coasting not
coasting coasting
0008
bit 4
emergency off
not in emergency off
in emergency off
0010
bit 5
for inverter use
bit 6
for inverter use
bit 7
for inverter use
Table 6 : Inverter Status 2 (register 0F)
Upper
Byte
Bit Inverter
Status
0
1
Single-Bit
Read Mask
bit
0
accelerating not
accelerating accelerating 0001
bit
1
decelerating not
decelerating decelerating 0002
bit 2
for inverter use
bit
3
retry
not
retrying
retrying
0008
bit 4
running (including DC
injection braking)
stopped running
0010
bit 5
for inverter use
bit 6
for inverter use
bit
7
tripped not
tripped tripped
0080