Toshiba G3 TOSVERT-130 Manuale Utente

Pagina di 62
 
 33
11.2
11.2
11.2
11.2      Read/Write Registers
 Read/Write Registers
 Read/Write Registers
 Read/Write Registers    
11.2.1
11.2.1
11.2.1
11.2.1     GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1    
 
Register 
Function / Title 
Bank 
Mask 
Adjustment Range 
Multiplier 
26 
MAXIMUM OUTPUT
FREQUENCY
 
(
∗∗∗∗
)
0 / 1 
FFFF 
0BB8 
 9C40 (30.00
400.00) 
0.01 
27 
BASE FREQUENCY #1
0 / 1 
FFFF 
09C4 
 9C40 (25.00
400.00) 
0.01 
28 
BASE FREQUENCY
VOLTAGE SELECT
 
(
∗∗∗∗
)
0 / 1 
0030 
0000: Input voltage level 
(0) 
0020: Automatic setting 
(1) 
0030: Stationary setting 
(2) 
 
29 
MAXIMUM OUTPUT
VOLTAGE #1
0 / 1 
FFFF 
0000 
 0258 (0 
 600) 
2A 
REVERSE OPERATION
DISABLE SELECT
0 / 1 
0020 
0000: Reverse allowed 
(0) 
0020: Reverse not allowed 
(1) 
 
2B 
UPPER LIMIT FREQUENCY
0 / 1 
FFFF 
0000 ~ Fmax 
0.01 
2C 
LOWER LIMIT FREQUENCY
0 / 1 
FFFF 
0000 
 UL, Fmax 
0.01 
2D 
VOLTS PER HERTZ
PATTERN
 
(
∗∗∗∗
)
0 / 1 
000F 
0000: Constant torque 
(1) 
0001: Variable torque 
(2) 
0002: Auto. torque boost 
(3) 
0006: #3 w/ auto. energy savings  (4) 
000A: Vector control 
(5) 
000E: #5 w/ auto. energy savings  (6) 
 
2E 1, 
VOLTAGE BOOST #1
0 / 1 
FFFF 
0000 
 012C (0.0 
 30.0) 
0.1 
2F 
ACCELERATION TIME #1
0 / 1 
FFFF 
0001 
 EA60 (0.01~ 600.00) 
0001 
 EA60 (0.1~ 6000.0) 
0.01 
0.1 
30 
DECELERATION TIME #1
0 / 1 
FFFF 
0001 
 EA60 (0.01~ 600.00) 
0001 
 EA60 (0.1~ 6000.0) 
0.01 
0.1 
31 
ACC/DEC PATTERN #1
SELECTION
0 / 1 
0030 
0000: Linear 
(0) 
0010: Self-adjusting 
(1) 
0020: S-Pattern #1 
(2) 
0030: S-Pattern #2 
(3) 
 
32 
ACCEL/DECEL PATTERN
ADJUST LOW
0 / 1 
00FF 
0003 ~ 00FD  (0 
 50) 
(Note 1) 
33 
ACCEL/DECEL PATTERN
ADJUST HIGH
0 / 1 
00FF 
0003 ~ 00FD  (0 
 50) 
(Note 1) 
Note 1:  Register data = (desired setting x 5 + 3), converted to hexadecimal