T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2666—02
12
a
On: Continuous fan operation during occupied periods. During not occupied periods and in standby mode when no motion is 
sensed, fan cycles with call for heat or cool.
Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details).
NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress):
ten seconds: when returning from temporary setpoint changes, info screen, temp occ, and temp not occ.
one minute: when returning from setting clock/day.
ten minutes: when returning from System Checkout.
five minutes: when returning from all other modes.
Special Functions
Restore Factory Configuration (Run/Clear)
IMPORTANT
This operation erases current configuration and 
restores factory defaults for all configuration, 
parameters, setpoints and schedules. To regain the 
old requires device reconfiguration.
1. Press both Run Schedule and Clear Start Time.
2. The display gives the option to revert to FAC CFG.
a. To restore the factory defaults, press up
or 
down
until the display indicates YES.
b. To cancel this option, ensure the display 
indicates NO.
3. Press Run Schedule.
Get Factory Schedule (Info/Clear)
Performing this operation reverts the schedules to the factory 
defaults:
1. Press both Info and Clear Start Time.
2. The display gives the option to revert to FAC SCH.
a. To restore the factory schedule, press up
or 
down
until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule.
Test Mode (Occupied/Not Occupied/
Schedule Day)
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is 
cycled too quickly.
The minimum off time for compressors is bypassed 
during Test Mode. Equipment damage can occur if the 
compressor is cycled too quickly.
Use the Test Mode to check the thermostat configurations and 
operation. To start the system test:
1. Press Schedule Day, Occupied and Not Occupied 
simultaneously.
2. The display gives the option to TEST.
a. To enter test mode, press up
or down
until the 
display indicates IN TEST.
b. To cancel this option, ensure display indicates NO 
TEST.
3. Press Run Schedule.
NOTES:
To verify whether or not the system test is still 
active, repeat the above process.
The system test times out after ten minutes with no 
key pressed.
Save User Schedule (Info/Copy)
Performing this operation saves the current schedule 
(including holidays) to memory, overwriting the old saved 
schedule:
1. Press both Info and Copy.
2. The display gives the option to revert to SAV SHD.
a. To save the current schedule, press up
or 
down
until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule.
Get User Schedule (Info/Run)
Getting the user schedule restores the schedule (including 
holidays) from saved memory, overwriting the schedule 
currently in use:
1. Press both Run Schedule and Info.
2. The display gives the option to GET SHD.
a. To retrieve the saved schedule, press up
or 
down
until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule
OPERATION
Startup Operation
Upon initial thermostat power-up, a startup and initialization 
program begins. This startup occurs only on initial power-up. 
After total loss of power for an extended period, the current 
time and day can be lost (requiring reset). However, the 
thermostat retains the user program.
NOTE: With no program set, the thermostat controls to the 
Occupied default setpoints of 70° F (21° C) for heat 
and 75° F (24° C) for cool.
Schedule
Fan
Selects fan operation mode. Toggles between On and Auto.
a
Run Schedule
Resumes running schedule (cancels Temporary Occupied action, Holiday, and/or 
Temporary setpoint changes.)
Table 7. T7351 Key Function Summary. (Continued)
Grouping
Button
Definition