Cisco CATALYST 6509E 9 SLOT 15U CHASSIS NO POWER SUPPLY NO FAN TRAY Guida Specifiche

Pagina di 336
4-46
Catalyst 6500 Series Switches Installation Guide
OL-5781-04
Chapter 4      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Step 10
From the left side of the power supply, connect the DC-input wires to the left power supply terminal 
block (
) in this order:
1.
Ground 
2.
Negative (-) 
3.
Positive (+) 
Note
When you tighten the terminal nuts, make sure that they are snug. Do not overtighten them. 
Overtightening the terminal nuts can break the terminal block. (Maximum torque: 
36 inch-pounds.)
Step 11
From the left side of the power supply, connect the DC-input wires to the right power supply terminal 
block (
) in this order:
1.
Negative (-) 
2.
Positive (+) 
Note
When you tighten the terminal nuts, make sure that they are snug. Do not overtighten them. 
Overtightening the terminal nuts can break the terminal block. (Maximum torque: 
36 inch-pounds.)
Figure 4-36 DC-Input Wire Connections for 4000 W Operation (Left-Side Power Bay)
114008
3
INPUT OK
FAN
OK
OUTPUT
FAIL
I
0
1
2
Captive 
installation
screw
(   ) Ground
(+)  Positive
( - ) Negative
Power
switch
(   ) Ground
(+)  Positive
( - ) Negative
Power leads
attached to
terminal block
Terminal
block cover
Plastic
insulator
Power leads
attached to
terminal block
(+)   Positive
( - )  Negative
Terminal
block cover
Plastic