Catalyst 6500 Series Switches Installation Guide
OL-5781-04
Chapter 4 Removal and Replacement Procedures
Removing and Installing the AC-Input Power Supplies
Figure 4-5
Handling a 2700 W AC-Input Power Supply
Step 6
If the power supply bay is to remain empty, install a blank power supply filler plate (Cisco
part number 800-16727-01) over the opening and secure it with the captive installation screws.
part number 800-16727-01) over the opening and secure it with the captive installation screws.
Installing a 2700 W AC-Input Power Supply
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations. Statement 1045
installation. Install only in accordance with national and local wiring regulations. Statement 1045
To install an AC-input power supply, follow these steps:
Step 1
Ensure that the system (earth) ground connection has been made. For ground connection instructions,
see the
see the
.
Step 2
If necessary, remove the blank power supply filler plate from the chassis power supply bay opening by
loosening the captive installation screws.
loosening the captive installation screws.
Step 3
Verify that the power switch on the power supply is in the Off (0) position.
Step 4
Grasp both power supply handles. (See
.) Slide the power supply into the power supply bay.
Make sure that the power supply is fully seated in the bay.
Step 5
Securely tighten the power supply captive installation screws.
130890
ALL FASTERNERS MUST BE FULLY ENGAGED
PRIOR TO OPERATING THE POWER SUPPLY
PWR-2700-AC
ALL FASTERNERS MUST BE FULLY ENGAGED
PRIOR TO OPERATING THE POWER SUPPLY
PWR-2700-AC