49
ohms if being measured from the metal shell of the device). The ground resistance of a
soldering iron tip should be less than 20 ohms.
A factory building should be equipped with antistatic ground cables, and antistatic
common ground points should be set up on each floor. The ground resistance of a factory
building should be less than 1 ohm. The resistance between a ground cable shared by
devices and an antistatic common ground point should be less than 1 ohm.
In an electrostatic discharge protected area (EPA), antistatic dual-circuit wrist straps
should be available, all wrist straps should be inserted into dedicated wrist strap jacks, and
tools, devices, and ground cables that are fixed, except antistatic wrist straps and mobile
device tools, must not be grounded using alligator clips.
Ensure that tools' and devices' antistatic ground points are connected to antistatic
ground cables in parallel. Antistatic common ground bars are preferred, and series
connections are prohibited.
Ensure that SMT devices, board-assembled devices, devices used to assemble and
commission modules and systems, and devices/tools with antistatic ground points (for
example, a soldering iron) are grounded using separate antistatic ground cables. That is,
separate ground cables are connected from metal ground parts of the devices/tools to
antistatic ground cables, to ensure that the devices/tools are reliably grounded.
Set up EPAs according to ANSI/ESD S20.20 and IEC 61340-5-1 (international standard
systems for ESD protection), and ensure that the electrostatic sensitivity (HBM) is less than
100 V. That is, devices with the electrostatic sensitivity equal to or greater than 100 V can be
effectively protected in EPAs.
Take antistatic measures for static-electricity-generating articles that are required in an
EPA (for example, plastic parts, devices, and monitors used in the assembly procedure), for
example, using an ionizing air blower, applying antistatic liquid, and using a static shielding
bag/net. Ensure that electrostatic sensitive devices, boards, and components are 30 cm or
more away from non-eliminable static-electricity-generating sources. Within the range 30 cm
away from electrostatic sensitive devices, boards, and components, ensure that the friction
voltage is less than 100 V.
Use tools made of antistatic materials to turn over electrostatic sensitive devices,
boards, and components, for example, antistatic foam, antistatic boxes, antistatic
vacuum-formed plastic boxes, antistatic tote carts, and antistatic shielding bags. Do not
place electrostatic sensitive devices, boards, and components directly in containers without
ESD protection, for example, ordinary EPE trays, ordinary vacuum-formed plastic boxes,
ordinary plastic bags, ordinary plastic boxes, ordinary hollow boxes, and tote carts without
ESD protection.
Before transporting electrostatic sensitive devices, boards, and components in non-EPA
areas, for example, trans-plant transportation, perform antistatic closed packaging for the