MAINTENANCE
This networked emergency ballast automatically performs required routine testing. Results are reported to
maintenance personnel via the indicator light and audible alarm. The results are also reported to the hub and
this test data can be viewed at a designated PC (software provided separately).
Note:  If optional audible alarm is disabled, maintenance personnel should periodically check the indicator
light. If the indicator light is flashing, go through all steps of Troubleshooting Guide.
Failure Status will be reset when the unit passes:
• The next automatic test, or
• A manual test exceeding 15 seconds, or
• An actual power failure exceeding 15 seconds, or
• A user-generated test via FEBnet network PC (see user's manual
provided with FEBnet system software).
TROUBLESHOOTING GUIDE
NOTE: It is normal for the indicator light to remain off for a few
minutes on initial start-up or after a very long power outage
(discharge), as the battery voltage rises to normal range.
Refer to the Troubleshooting Guide if this condition persists.
STATUS INDICATORS
INDICATOR
LIGHT
AUDIBLE
ALARM
PROBLEM
CORRECTION
Unit is Operating Correctly.
None
No beeping
Light on
steady, not
flashing
Flashing
1/2
Second
Intervals
Beeping
1/2
Second
Intervals
Line voltage;
incorrect
installation
Check line voltage. For 120 VAC use black as hot;
   for 277 VAC use orange as hot wire lead.
Let battery charge. If after an hour failure is still
indicated, see action below.
1.Check to make sure lamps are good
(operational and specified for self-testing
emergency ballast) and in place.
2.Check to see if brown connector is properly
used.  (See Table 1.)
3.Check that fixture wiring is in accordance
with proper wiring diagram.
4.Allow unit to charge for 24 hours. Perform
manual test. If flashing/beeping continue,
emergency ballast should be replaced.
Flashing
1/2
Second
Intervals
Beeping
4 times
every 30
seconds.
Failed scheduled
self-test
Battery voltage
is outside limits.
Any other erroneous
 status indications
Corrupted chip
memory
Open inverter connector (red and white wires)
and push manual test switch for 15 seconds
minimum, then reconnect inverter connector.
Flashing
2 times
every 6
seconds.
Beeping
2 times
every 6
seconds.
None
The unit is running
it's user indicated
location scheme
Either:
• Wait 30 minutes for indicators to stop, or
• Use FEBnet network PC (see user's manual
provided with FEBnet system software)
4