PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0  10/10/2013
FWSG
Operations
2.6.4  SLC Configuration
The FWSG,
Communicates with the control panel via the SLC circuit. 
Is a FlashScan only device. 
CLIP mode is not supported. 
Is only compatible with Fire Alarm Control Panels version 21 or higher.
Occupies one module SLC address.  Set the address using the rotary dials on the FWSG prior 
to installation. 
The point uses the following configuration parameters:
Module Type: Monitor
Type Code Label: RF GATEWAY
Flash Scan Type: RF GATEWAY
An FWSG does not initiate alarms but the point is used for event reporting.
2.7  Operations
2.7.1  FWSG Modes Of Operation
Figure 2.10  FWSG Modes Of Operation
Start Up
Startup is a temporary mode of operation.  It is during the startup mode, a profile can be created or  
removed.  The startup period lasts for 10 seconds.  If a particular unit contains a profile, the LEDs 
blink yellow twice every second.  If the unit does not contain a profile, the LEDs blink red twice 
every second.  
During startup, the FWSG does not provide fire protection.
After startup, the FWSG proceeds to the factory default state if a profile was removed or missing.   
In the presence of a profile, the FWSG will proceed to mesh formation if it was previously part of 
a mesh network or normal mode if it was not previously part of a mesh network.  The FWSG does 
not respond to the FACP during startup mode.