PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0  10/10/2013
FWSG
Operations
The FWSG reports an ‘OPTIMIZING MESH’ or ‘OPT MS’ trouble to the FACP.  The FWSG 
reports “Optimization” to the communicator display of the PC Tools application.
Normal Mode
Normal mode can be described as a standard operating state. The mesh network is formed, provid-
ing fire protection.  The mesh network continuously searches for additional devices with a match-
ing profile to join the mesh.  To avoid interference,  the mesh network periodically checks for 
adjacent mesh networks created by Honeywell.  The FWSG reports “Normal” to the communicator 
display of the PC Tools application.
Rescue Mode
During normal mode, when a device loses communication to the network, the FWSG triggers the 
rescue mode in all communicating devices. All devices in communication continue to provide fire 
protection during rescue mode; but also search for a lost or added device.  The rescue mode termi-
nates automatically 6 minutes after the last device is rescued and returns to the normal mode.  The 
FWSG does not report trouble during rescue mode.  The FWSG reports “Rescue” to the communi-
cator display of the PC Tools application.
Mesh Optimization
In addition to the initial mesh optimization, the routine executes after any large change to the net-
work configuration or to recover from a link failure (class A fault).  Mesh optimization that occurs 
during the normal mode does not generate a trouble and provides fire protection from all devices 
that are participating in the mesh communication. The FWSG reports “Optimization” to the com-
municator display of the PC Tools application.
Bootloader
The FWSG enters the bootloader mode when it is being updated using the PC Tools application.  
The FWSG does not communicate with the FACP during bootloader mode.  The FWSG reports 
“Bootloader” to the communicator display of the PC Tools application.
2.7.2  Magnet Sensor Activations
Profile Magnetic Sensor
The profile magnetic sensor (Figure 2.9, “Profile Magnetic Sensor on FWSG”) is used to create a 
unique profile on startup.  It can also be used to start profile distribution for a FWSG that contains a 
profile.  The LED next to the profile magnetic sensor emits solid red light for ½ a second when the 
sensor is activated.
Mesh Formation Magnetic Sensor
toggles the FWSG, in and out of mesh formation mode.  The initial activation of the sensor puts the 
FWSG in mesh formation mode (as long as it contains a profile). A subsequent activation of the 
magnetic sensor toggles the FWSG out of mesh formation and into the initial mesh optimization 
and normal mode. The FWSG can be placed back into mesh formation by activating the magnet 
sensor once again.  The Mesh formation magnetic sensor can also be used to create a profile on 
startup for a FWSG that does not already contain a profile.
The LED next to the mesh formation magnetic sensor emits solid red light for ½ a second when the 
sensor is activated. 
2.7.3  LED Indications
The two LEDs on the FWSG blink in the same pattern to allow the LED to be viewed from any 
angle.  The LED indications are provided in the table below.