Honeywell International Inc. WFSADPT Manuale Utente
28
PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013
FWSG
Operations
2.7.4 Lock/Unlock FWSG
The FWSG can be locked to prevent access to the magnetic sensors, and to password-protect all
wireless interactions. The lock function can be performed by the PC Tool or by the FACP. When
the PC Tool is used to lock the FWSG, a password must be provided for all future interactions,
including unlocking the FWSG. When the FWSG is locked by the FACP for the first time, a default
password of "12345" is applied. If the FWSG was previously locked with a password from the PC
tools, the previous password will be applied. Use this password for all future interactions from the
PC Tools application.
Lock/Unlock FWSG through FACP
The lock/unlock function for the NFS2-3030 is accessible using the point programming menu. For
more information refer to the NFS2-3030 manual, part number LS10006-051NF-E.
Lock/Unlock FWSG through PC tools
To lock/unlock FWSG through PC tools, perform the following steps:
1. Connect the W-USB dongle device to your computer. For more information on USB dongle,
1. Connect the W-USB dongle device to your computer. For more information on USB dongle,
2. Launch the PC Tools application. Refer to Appendix B: "PC Tools" to know about launching
the PC Tools application.
3. Go to Site Survey, Create Mesh Network, or Diagnostics step.
4. Click Extras. The following screen is displayed.
4. Click Extras. The following screen is displayed.
5. Select Lock/Unlock Gateway. The Lock/Unlock gateway screen appears, displaying the
FWSG that is locked.
6. To lock or unlock the gateway, click Lock or Unlock as required.
• Lock - The Lock Gateway screen is displayed. Create a password and click Lock. The
gateway is locked.
• Unlock - The Enter password for Gateway screen is displayed. Enter the password and
click Unlock. The FWSG is unlocked.