Password Reset
To reset the password, contact technical support.
2.7.5  Weak Link Trouble Reporting
The Notifier Wireless Sensor Network uses two paths of communication for each device.  To estab-
lish the link between devices as a viable communication path, the signal strengths must meet the 
limits provided in Section 2.3, “Specifications”.  The Wireless Sensor Network implements a 
higher threshold for primary connections to provide an extra layer of robustness and immunity 
from interference.  A weak link trouble condition is initiated for any device that does not have at 
least one connection at the primary threshold.  This is an optional setting that can be disabled to 
ignore the weak link trouble condition.  The trouble can be disabled at the FWSG or at the FACP 
(NFS2-3030 only).  Disabling the trouble reporting at the panel will prevent the event from regis-
tering as a trouble but still enters into history as a background event.  Disabling the trouble report-
ing at the FWSG prevents the event from being reported to the FACP as a trouble or a non-trouble 
event.  To have trouble reporting enabled, turn the settings on at both locations.
Disabling Trouble Reporting at the FWSG Using PC Tools
To disable trouble reporting at the FWSG through PC tools, perform the following steps:
1. Connect the W-USB dongle device to your computer.  For more information on USB dongle, 
2. Launch the PC Tools application.  Refer to Appendix B: "PC Tools" to know about launching 
the PC Tools application.
3. Go to Diagnostics step.
4. Choose the FWSG from the communicator pane.
5. Click View Mesh.
6. Click Advanced Functions.  A drop-down list is displayed.