PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013  
49
Device Operations
Devices
3.7.3  Trouble States
The following trouble states are unique to the battery powered RF devices.  Multiple troubles states 
may be active for a single device, but only the highest priority trouble event will be displayed.
Trouble States with Fire Protection
The devices indicate the following trouble states with a single yellow LED blink every 13.6 sec-
onds. The wireless device will still perform fire protection during the following trouble states.
Class A Fault
The Class A fault denotes a single connection path from the device. The wireless system is a Class 
A system requiring two communication paths for normal operations. To remedy the Class A fault, 
ensure adequate device spacing or the use of a repeater may be required. The wireless mesh is a self 
healing network.  If the trouble is not cleared within 5 minutes, additional actions may be required.    
Refer to the troubleshooting section for tips on resolving Class A fault conditions.
The panel will display "CLASS A FAULT" or "CL A" during a Class A fault condition.
Weak Link
The weak link trouble denotes a connection of insufficient primary signal strength. If you come 
across such a trouble, ensure adequate device spacing, or the use of a repeater may be required.  
Tamper the device when moving it to a new location.  When the tamper condition is cleared, the 
FWSG will re-evaluate the signal strength connectivity with the neighboring devices and select the 
suitable signal paths.  Weak link trouble reporting can be disabled at the FACP or at the FWSG for 
installations not requiring primary link connectivity.  Refer to section 2.7.5 for more information on 
disabling weak link trouble reporting.  Refer to the troubleshooting section for more instructions on 
resolving a weak link condition.  
The panel displays "WEAK LINK FAULT" or "WEAK" for a device that is in the weak link condi-
tion. 
Low Battery
The low battery event denotes that:
• The device has less than one month power left to perform the required operations.
 Or 
• Presence of less than four viable batteries.
The low battery event is a latching condition.  To clear the low battery event, tamper the device and 
replace all the four batteries. When a device is tampered, it drops out of the mesh network and 
attempts to rejoin as soon as the batteries are replaced and the tamper event is cleared.  If the device 
has dropped from the mesh prior to the tamper event, a system reset has to be issued to clear the 
low battery trouble.  The panel displays "BATTERY LOW " or "BAT LOW" during a low battery 
condition.
Trouble States without Fire Protection
Tamper
A tamper trouble indicates that a detector is not firmly attached to the base or, in a module, the 
cover plate is not properly attached.  The tamper condition is annunciated in the following ways:
Device Indication  The LED on the device emits yellow light for 4 seconds followed by a yellow 
blink once every 12 seconds immediately after the tamper condition.