PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013  
51
Device Operations
Devices
3.7.4  Background Events
The following conditions are not considered a trouble, supervisory, or alarm condition.  These 
events are stored in history of the FACP.
Pre-Class A Fault
A device will report a pre-Class A event when it first identifies a single connection path condition.  
If the connection path is not restored or replaced with another viable connection path within 180 
seconds a Class A fault condition will be reported.  The history event  reports this condition as 
“PRE-CLASS A FAULT”.
Device Drop
A device will report a device drop if it has lost complete communication with the mesh network.  If 
the device does not recover in 180 seconds or less, a "NO ANSWER" or "INVREP" trouble is 
reported for the address.  The history event will report as a “DEVICE DROPPED”.
Weak Link
When weak link reporting is enabled by the FWSG and disabled in the FACP, then all weak link 
conditions will be entered as background events in history.  The history event is reported as a 
"WEAK LINK FAULT" or "WEAK" for a device that is in the weak link condition.