Honeywell International Inc. WFSLCDUI Manuale Utente

Pagina di 96
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013  
19
Configuration and Programming
W-GATE
2.6  Configuration and Programming
The goal of configuring and/or programming the W-GATE is to:
1.
Create a profile - A profile is a set of parameters that binds together a W-GATE and the devices 
in a mesh network. 
2.
Distribute the profile to every device that will be a part of the mesh.
3.
Form the mesh - The mesh cannot be formed until the profile is assigned to the W-GATE. The 
profile contains a mesh ID and, if required, a password, that are used when forming the 
associations. Creating and distributing the profile will enable all the devices that have that 
profile to form associative links when the mesh is formed. All devices, including the W-GATE, 
require a common profile.
This section shows how to configure/program an W-GATE with a profile, how to distribute that 
profile to other devices, and how to form all these devices into a mesh. These processes may be per-
formed with or without using PC-based configuration tool.
2.6.1  Without a PC-based Configuration Tool
This section shows the configuration of the W-GATE using only a magnet and a screw driver. For 
configuration instructions using the PC-based configuration tool, refer to 2.6.2, "With a PC-based 
Configuration Tool". 
There are two ways to provide a W-GATE with a profile without using a configuration tool.
Create a new profile using the W-GATE
Assign a previously created profile to the W-GATE using a distributor.
Create a New Profile
To create a unique profile in the W-GATE without using the PC-based configuration tool, perform 
the following steps.
1.
Start with the device powered off.  The process is performed during the start-up. 
2.
Power on the W-GATE using SLC power or external +24V.  This can be done either by 
attaching the W-GATE to its mounting plate with the terminals already energized, or by 
connecting the SLC or external source wiring to a W-GATE that is already installed in its 
mounting plate.
3.
Verify if the W-GATE is in the factory default state; if it is in the factory default state, both the 
LEDs on the W-GATE flash red (double blink) every second for ten seconds.  If the LEDs are 
yellow, refer to section below on removing a profile.
Figure 2.7  W-GATE with LEDs and Magnetic sensors