PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013  
21
Configuration and Programming
W-GATE
Figure 2.8  Mesh Formation 
Magnetic Sensor on a W-GATE
The W-GATE transitions to the mesh for-
mation mode and establishes communica-
tion with all the devices containing a 
common profile.  The blink pattern in W-
GATE indicates that it is in mesh forma-
tion mode. 
•At this stage, both the LEDs on the W- 
  GATE blinks twice every 3.4 seconds. 
•The first blink is green and the second
  blink is red when the W-GATE is acting
  as a profile distributor and forming the 
mesh. 
The first blink is green and the second blink is yellow when the W-GATE is only forming the 
mesh. 
Mesh formation typically takes one minute for each device in the mesh. Mesh formation automati-
cally terminates 10 minutes after the last device joins the mesh.  The mesh formation can be termi-
nated manually by the user by activating the mesh formation magnetic sensor again. 
Once the mesh formation is complete, the network transitions to optimize the mesh. For further 
operating instructions, refer to 2.7, "Operations".
2.6.2  With a PC-based Configuration Tool
Assign Profile with PC Tools
To assign a profile to the W-GATE using the PC Tools application, do the following:
1.
Connect the W-USB dongle device to your computer.  For more information on USB dongle, 
refer to Section 5:, "USB Adapter".
2.
Launch the PC Tools application.  Refer to Appendix B:, "PC tools" to know about launching 
the PC Tools application.
3.
Go to the Create Mesh Network step.
4.
Create a new profile or import an existing profile as required.
5.
Select and open the profile to be assigned to the W-GATE from the Name drop-down list in the 
left panel.
6.
Power on the W-GATE in range of the PC Tools.