Operations
W-GATE
2.7 Operations
2.7.1 W-GATE Modes of Operation
Figure 2.10 W-GATE Modes Of Operation
Start Up
Startup is a temporary mode of operation. It is during the startup mode, that a profile can be created
or removed. The startup period lasts for 10 seconds. If a particular unit contains a profile, the LEDs
blink yellow twice every second. If the unit does not contain a profile, the LEDs blink red twice
every second.
or removed. The startup period lasts for 10 seconds. If a particular unit contains a profile, the LEDs
blink yellow twice every second. If the unit does not contain a profile, the LEDs blink red twice
every second.
During startup, the W-GATE does not provide fire protection.
After startup, the W-GATE proceeds to the factory default state if a profile was removed or miss-
ing. In the presence of a profile, the W-GATE will proceed to mesh formation if it was previously
part of a mesh network or normal mode if it was not previously part of a mesh network.
ing. In the presence of a profile, the W-GATE will proceed to mesh formation if it was previously
part of a mesh network or normal mode if it was not previously part of a mesh network.
The W-GATE does not respond to the panel during startup. All the three SLC addresses will be an
INVALID REPLY.
INVALID REPLY.
Factory Default
Factory default is the initial state of the W-GATE. The W-GATE and peripheral devices do not pro-
vide any fire protection when they are in factory default mode. The W-GATE does not communi-
cate with wireless devices. The only wireless communication is with the configuration tool. The
configuration tool needs to be within 20 feet of the W-GATE for communication. The W-GATE
needs to be assigned a profile before continuing the installation.
vide any fire protection when they are in factory default mode. The W-GATE does not communi-
cate with wireless devices. The only wireless communication is with the configuration tool. The
configuration tool needs to be within 20 feet of the W-GATE for communication. The W-GATE
needs to be assigned a profile before continuing the installation.
The W-GATE reports “Factory Default” to the communicator display of the PC Tools application.
The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also
be normal. The trouble point (base address + 2) will indicate open circuit.
be normal. The trouble point (base address + 2) will indicate open circuit.
Profile Configured
The W-GATE enters the profile configured mode after getting assigned a profile from the tool or a
distributor or creating a profile. Profile configured is a temporary mode before the W-GATE transi-
tions to mesh formation or normal mode.
distributor or creating a profile. Profile configured is a temporary mode before the W-GATE transi-
tions to mesh formation or normal mode.
The W-GATE does not provide fire protection in the profile configured mode. The W-GATE
reports “Profile Assigned” to the communicator display of the PC Tools application.
reports “Profile Assigned” to the communicator display of the PC Tools application.
The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also
be normal. The trouble point (base address + 2) will indicate open circuit.
be normal. The trouble point (base address + 2) will indicate open circuit.