PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013  
25
Operations
W-GATE
2.7  Operations
2.7.1  W-GATE Modes of Operation
Figure 2.10  W-GATE Modes Of Operation
Start Up
Startup is a temporary mode of operation. It is during the startup mode, that a profile can be created 
or removed. The startup period lasts for 10 seconds. If a particular unit contains a profile, the LEDs 
blink yellow twice every second. If the unit does not contain a profile, the LEDs blink red twice 
every second.  
During startup, the W-GATE does not provide fire protection. 
After startup, the W-GATE  proceeds to the factory default state if a profile was removed or miss-
ing.  In the presence of a profile, the W-GATE will proceed to mesh formation if it was previously 
part of a mesh network or normal mode if it was not previously part of a mesh network. 
The W-GATE does not respond to the panel during startup.   All the three SLC addresses will be an 
INVALID REPLY.
Factory Default
Factory default is the initial state of the W-GATE. The W-GATE and peripheral devices do not pro-
vide any fire protection when they are in factory default mode. The W-GATE does not communi-
cate with wireless devices. The only wireless communication is with the configuration tool. The 
configuration tool needs to be within 20 feet of the W-GATE for communication. The W-GATE 
needs to be assigned a profile before continuing the installation.
The W-GATE reports “Factory Default” to the communicator display of the PC Tools application.
The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also 
be normal.  The trouble point (base address + 2) will indicate open circuit.
Profile Configured
The W-GATE enters the profile configured mode after getting assigned a profile from the tool or a 
distributor or creating a profile.  Profile configured is a temporary mode before the W-GATE transi-
tions to mesh formation or normal mode.  
The W-GATE does not provide fire protection in the profile configured mode.  The W-GATE 
reports “Profile Assigned” to the communicator display of the PC Tools application.
The W-GATE’s base address will be normal and the supervisory point (base address + 1) will also 
be normal.  The trouble point (base address + 2) will indicate open circuit.