ZTE Corporation R8978S2600L Manuale Utente

Pagina di 66
ZXSDR R8978 User Manual
If...
Then...
distance transmission. A junction box is needed to convert the cables to
a different size.
The indoor DC power distribution unit (with a power switch) connects to
the lighting protection box of the indoor DC power supply.
Connect the junction box to the indoor DC power lighting protection
box (there are a total of three outputs in the indoor DC power lighting
protection box, each of which has an air switch and can be connected
to an
RRU
).
After the DC power cable is converted by the junction box, it can be
connected to the ZXSDR R8978.
The junction box is not required because the AC power supply is low with
a large voltage and voltage drop can be ignored.
Connect the indoor AC power distribution cabinet to the outdoor AC
power lightening protection box (there are a total of three outputs in the
indoor AC power distribution cabinet, each of which has a power switch
and can be connected to an
RRU
).
Use the AC power supply
without a junction box
Connect the outdoor AC power lightening protection box to the ZXSDR
R8978.
illustrates the cable connection.
Figure 3-7 Connection of DC Power Input Cable
3-8
SJ-20141113151137-001|2016-08-17 (R1.2)