Controlled Electronic Management Systems Ltd INFOPROX Manuale Utente

Pagina di 79
InfoProx Entry   
 
Configuring the Door Control Unit 
Configure Inputs 
Note 
DO NOT CHANGE FACTORY INPUTS WITHOUT CONSULTING WITH 
TECHNICAL SUPPORT. 
This screen appears after Config TZ Type.  
 
Config I/Ps 
0-Yes, Other-No 
There are four inputs for the unit: 0 monitors door position; 1 monitors lock status; 
2 monitors RTE/RTX switch status and 3 is a spare input. Input configurations are 
set at the factory. Generally, these inputs should not be reconfigured and setup 
mode should be bypassed by pressing #. 
Doorstrike Time 
Door strike is the time a door lock remains open.  
After a card has been validated at the reader, the relay controlling the door lock is 
activated for the time set in Door Strike Time mode. During this timeframe, the 
door can be opened. If the cardholder does not open the door during this time, the 
door lock will relock and will not open. The default setting is five seconds. 
 
Modifying the door strike time 
Pressing # at the end of Configure Inputs displays the following Door Strike 
Time
 prompt: 
 
Set Drsk= 05s 
New Drsk=   s 
1. 
Enter a two-digit number for the seconds desired for Door Strike 
Time
Once the time is set, the next screen in the Configuration menu 
sequence, Door Close After Time, automatically displays. 
 
 
This option can be bypassed by pressing the # key, 
accepting the default setting of five seconds. The 
Ù key can 
be used to correct any errors entering the Door strike time. 
 
Software House 
 
35