Controlled Electronic Management Systems Ltd S610MSCRM Manuale Utente
S610S Manual - Hardware Installer Manual - Version 1.8
12
Card Type
paragraph 10.6 in this manual
Read Head
paragraph 10.6
Auxiliary Devices
An Exit Reader and/or a DIU must be set as present using the reader’s diagnostic keypad.
3.4 Addressing an S610S master reader
Use the reader’s keypad to access the diagnostic menu to address an S610S.
Enter
followed by the reader PIN code. (Factory Default PIN 0000, or 9999 if the
reader has been added to the AC2000 Devices table and come online).
Default Reader PIN codes may have been changed, consult your System Administrator.
Default Reader PIN codes may have been changed, consult your System Administrator.
If incorrectly entering a pin, wait 5 seconds before trying again, to allow for timeout.
The following details will appear on the LCD panel: -
ADDRESSING AN S610S READER
On the master reader, use the
key to navigate to the Configuration menu.
Press
key.
Press
key again.
Enter the Decimal address value of the reader in two digits e.g.
02
for reader 2 or
14
for reader 14.
After entering the reader address, Press the
key to enter
OK
.
Do nothing to cancel and start over, or press
to confirm
OK
new address.
Illustration below shows Reader addresses 3, 0 and 7 are used on Port 1, Controller A
Controller
S600S
TCP/IP
RS485
ACCESS CONTROL SYSTEM
TCP/IP
S610S EXIT
A
1
S610S
EXIT
0
A
1
1
0
A
1
0
7
A
1
1
7
A
1
0
PORT
3
A
1
0
Example of used Reader addresses.