FreeWave Technologies Inc. 1521131FFF Manuale Utente

Pagina di 62
 Spread Spectrum Wireless Data Transceiver User Manual 
LUM0002AG Rev A 
Version 7.0 
23 
Setup Port (D) 
Note: DO NOT change this setting unless the correct programming cable is 
available for the new setting.  
 
This setting determines which port, Main or Diagnostics, is used to enter the Setup 
Main Menu.    
Menu Port 
Additional 
Information 
  1 
Main Only 
The terminal is connected to the Main Data Port.    
  2 
Diagnostics Only 
The terminal is connected to the Diagnostic Port. 
  3 
Both Ports 
The terminal may be connected to either port. 
The factory setting is based on the type of transceiver.  A setting of “2” will be used 
with Ethernet products and Mirrored Bit products, a setting of ”3” will be used 
otherwise.  Setup mode is invoked by sending a "U" (Shift-U) to the Diagnostics 
port or by pressing/toggling the Set-up button/switch, if available.  OEM boards 
may also enter Setup when Pin 2 is grounded.  The Ethernet reset button will NOT 
put the unit into Setup mode. Ethernet transceivers must use the “U” option. 
The Main Data Port is the RS232 port. The Diagnostics port is a 3-pin connector 
on the rear panel of the FGR2-CE and the OEM “Mini” series transceivers. The 
diagnostic cable for this port (ASC0409DC) is available from FreeWave.  The 
FGR2-C OEM modules use a 2-row, 2 mm female connector. The diagnostic cable 
for this port (ASC2009DC) is available from FreeWave. 
TurnOn/OffDelay 
(E)  
TurnOnDelay- Sets the delay between when the line drivers are turned on and 
when the data leaves the data port.  This setting can be adjusted for a 1-9mS 
delay. 
TurnOffDelay- This setting specifies the time after the end of transmission of a 
character to the RS485 bus that the transceiver stops driving the bus and releases 
the bus to other devices. The units are ¼ of a character with a range of 0-9. An 
entry of 4 means a delay equivalent to the duration of a full character.  Default is 
zero delay. 
For data rates of 1200 bits/S or slower, avoid setting the TurnoffDelay parameter 
higher than 4.  At those rates the functionality of the microprocessor changes so 
that a TurnoffDelay of 5 will have the same effect as if set to 1, and a setting of 6 
will have the same effect as 2, and so on. 
Note: TurnOffDelay must be set to a value of at least 4 for RS4xx operation. 
FlowControl (F) 
This menu specifies the hardware flow control for the Data port. The options for 0-3 
are described below. 
Menu Port Additional 
Information 
   0                        None                Default - Uses software control (XON XOFF) 
   1 
RTS 
Uses Standard RTS/CTS control lines 
   2 
 DTR 
 
   3 
                DOT