Honeywell International Inc. W8735ER01 Manuale Utente

Pagina di 8
W8735ER WIRELESS OUTDOOR RESET MODULE
5
66-1202—01
(design temperature) is the point at which the boiler should be 
set to its high limit setting. Setting the boiler temperature too 
low during the coldest periods will result in the inability to keep 
up with heat demand. This is the critical setting in avoiding 
call-backs.
High Outdoor Temperature: This is the outdoor temperature 
for which the Low Boiler Temperature is set. This is the 
parameter that most impacts energy savings. Setting the High 
Outdoor Temperature too high results in less energy savings 
as the boiler may run at a higher temperature during warmer 
weather than necessary to maintain comfort in the space. 
Setting this parameter too low will result in too narrow a range 
for the control to be adjusting boiler temperature. In most 
cases the default of 40 °F (4.4 °C) is fine.
NOTE: In many cases these parameters will not need to 
be adjusted as their default values are designed 
to accommodate mid-Atlantic and lower New 
England areas.
CAUTION
Possible Equipment Damage
When enabling the Outdoor Reset function, be sure to 
refer to the boiler OEM’s instructions for the lowest 
return water setting to avoid condensation in the heat 
exchanger, which can result in equipment damage. 
1
Minimum values, Maximum values and Default High Limit 
settings shown are for the L7224U and the S9361 IBC. Val-
ues may change for other Aquastats and IBCs. Check the 
specific Aquastat and/or IBC Installation Instruction manual 
for more information on default settings.
Boost
If heat demand is not met within a certain time period while 
the boiler is in setback mode (following the Outdoor Reset 
curve), a Boost Period is invoked where the boiler set point is 
increased by a value called the Boost Step. Each time the 
Boost Period elapses and heat demand is not satisfied, the 
boiler set-point is again increased by the Boost
 Step, up to the 
maximum setting provided by the High Limit setting (see Table 
and Fig. 5). Boost is reset when the heat demand is satisfied 
(local or remote call for heating has ended). Simply reaching 
the boiler set-point does not reset the Boost. Continuous 
Boost calls may be an indication of a poorly set Outdoor Reset 
Curve for the environment or faulty equipment. For the 
Aquastat, a Boost warning will be indicated on the 3-digit 
Aquastat display if Boost is required on 60 consecutive cycles. 
For the Aquastat, the Boost Period can be set from OFF to a 
range of 5 minutes to 30 minutes, adjustable in 1 minute 
increments. The default setting is 10 minutes. The Boost Step 
can be set from Off to a range of 5 F (-15 C) to 20 F (-7 C).
For the IBC, the Boost Period is fixed at 30 minutes and the 
Boost Step is fixed at 5 °F. See Table 2.
1
 For the IBC, both the Boost Period and Boost Step are fixed 
parameters and can not be adjusted.
Warm Weather Shutdown - Aquastat
The Warm Weather Shutdown feature causes a “Warm Start” 
boiler to shut down when the outdoor temperature exceeds a 
specified value. Warm Start boilers maintain a minimum 
temperature by setting the Low Limit on the Aquastat. If 
enabled this features cancels the Low Limit setting when the 
outdoor temperature exceeds a specified value.
CAUTION
Zone Panel Settings
In applications with zoning panels having a priority 
zone for domestic hot water: Disable the warm 
weather shutdown feature on the Aquastat.
The Warm Weather Shutdown feature can be set from OFF to 
a range of 40 °F (4.4°C) to 70 °F (21 °C), adjustable in 10 
degree increments. The default setting is OFF. See Table 3.
Table 1. Outdoor Reset Curve Settings and Defaults.
1
Aquastat
Parameter
Minimum 
value
Maximum 
value
Default
High Limit
130 °F
(54 °C)
240 °F
(116 °C)
180 °F
(82 °C)
Minimum Outdoor 
Temperature
-40 °F
(-40 °C)
40 °F
(4.4 °C)
0 °F
(-18 °C)
Minimum Boiler 
temperature 
80 °F
(27 °C)
180 °F
(82 °C)
130 °F
(54 °C)
Maximum Outdoor 
Temperature
30 °F
(-1 °C)
70 °F
(21 °C)
40 °F
(4.4 °C)
IBC
Parameter
Minimum 
value
Maximum 
value
Default
High Limit
130 °F
(54 °C)
220 °F
(104 °C)
180 °F
(82 °C)
Minimum Outdoor 
Temperature
-40 °F
(-40 °C)
40 °F
(4.4 °C)
0 °F
(-18 °C)
Minimum Boiler 
temperature 
130 °F
(54 °C)
150 °F
(56 °C)
140 °F
(60 °C)
Maximum Outdoor 
Temperature
40°F
(12.7 °C)
70 °F
(21 °C)
40°F
(12.7°C)
Table 2. Boost Settings and Defaults.
Aquastat
Parameter name
Minimum 
value
Maximum 
Value
Default
Boost Period
5 minutes 
(or Off)
30 minutes
10 minutes
Boost Step
5 F (or Off)
20 F
10 F
IBC
Parameter name
Value
1
Boost Period
30 minutes
Boost Step
5 F (or Off)