Honeywell International Inc. W8735ER01 Manuale Utente

Pagina di 8
W8735ER WIRELESS OUTDOOR RESET MODULE
66-1202—01
4
OPERATION
General
The W8735ER Wireless Outdoor Reset Module is a device 
which when connected to an AquaReset enabled Electronic 
Aquastat, Integrated Boiler Control (IBC) or SOLA control via 
the EnviraCOM™ communication bus, enhances the available 
control features to include Outdoor Temperature Reset, a 
stepped Boost function as well as Warm Weather Shutdown 
to provide increased boiler efficiency while servicing the heat 
demand. Set-up of the Outdoor Setback curve as well as the 
Boost function is done using the 3-digit/3-button display on the 
L7224/L7248 Aquastat (see L7224 Installation Instructions 
Form Number 69-1720 and/or Form Number 68-0281 for 
more information). For the IBC setup see
 
Form Number 66-
1203 Installation Instructions for more information. For SOLA, 
set-up of the reset curve is done using the S7910 or S7999 
display (See Form Numbers 65-0315, 66-1175, and 68-0295 
for more information.)
Adjusting Aquastat and IBC Settings
To discourage unauthorized/unintentional changing of 
Aquastat and IBC settings, a procedure to enter the 
ADJUSTMENT mode is required. To enter the ADJUSTMENT 
mode, press the UP, DOWN, and I buttons (See Fig. 4) 
simultaneously for three seconds. Next, press the I button until 
the feature requiring adjustment is displayed then use the 
arrow up/down buttons to set the parameter value (See Table 
4). After 60 seconds without any button inputs, the controller 
will automatically return to the normal display mode.
Fig. 4. Location of L7224/L7248 and S936X 3-digit display and buttons.
Outdoor Reset
The Outdoor Reset feature adjusts the target boiler 
temperature to a point below its local high limit setting and 
above the boiler's condensation temperature by using the 
EnviraCOM communication bus to directly adjust the Aquastat 
set-point. Should a call for Domestic Hot Water be detected, 
the boiler temperature is commanded to return to the High 
Limit setting, ensuring a hot water supply is available. When 
the Domestic Hot Water demand is met, the Outdoor Reset 
feature is once again enabled. See Table 1 and Fig. 5.
Application and Settings Pointers
The energy savings concept behind Outdoor Reset is to 
minimize the energy in the boiler that is lost during the off 
cycle. This is accomplished by maintaining the boiler 
temperature as low as possible and/or running the boiler for 
longer periods of time. Although considerable energy savings 
exists, the boiler is only one part of the system that includes 
thermostats, other controls, and radiation. To maximize 
savings while avoiding call-backs due to uncomfortable 
homeowners, care must be taken when adjusting the control 
parameters. Listed below are operation and adjustment 
pointers. See Fig. 5.
Low Boiler Temperature: This is the minimum temperature 
at which the boiler is designed to operate. Setting this too low 
during warmer periods may result in condensation in the boiler 
and reduce boiler life. Typically this setting is 130 °F (54 °C) 
for gas boilers and 140 °F (60 °C) for oil boilers and is 
adjusted to be maintained at the high outdoor temperature 
setting. Some new cast iron boilers are designed to operate at 
lower temperatures. Consult the manufactures' specifications.
Low Outdoor Temperature: As the outdoor temperature 
decreases, the boiler temperature must increase to provide 
more heat to the space. The Low Outdoor Temperature 
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T 3
2
1
THREE-DIGIT 
DISPLAY
BUTTONS
M33913
GND
BUTTONS
THREE-DIGIT 
DISPLAY