Installation and Operations Guide 
AZW-5000
12
LTBT-TM-AZWIOG
Rev. 0001BETA
© Honeywell 
Commissioning
Commissioning requires temporarily wiring the device to the MS/TP network, 
opening it in a device template, and then editing the device’s settings. 
Commission the coordinator first. 
I M P O R TA N T
Write down the values you assign during this process. This 
information will be useful in troubleshooting problems should they arise. See 
“Appendix B: AZW-5000 Commissioning Record” on page  30.
To open the commissioning template
1.
Download device template 99100017.dvt from the Alerton Support 
Network and copy it to the Alerton\Standard\Displays folder.
2.
Start Envision for BACtalk.
3.
Open a data display in Edit mode and then add a Pushbutton Selector. 
4.
Double-click the pushbutton and select Device template (different 
device)
 as the button type. 
The Pushbutton Item dialog box appears.
5.
Enter the text for the button label (“AZW-5000 commissioning”, for 
example).
6.
Enter 9999 for the Device instance. 
7.
Select Use display from and then select the Alerton/Standard rep/job. 
8.
Select template number 99100017 and then click Close
9.
Exit Edit mode.
To commission AZW-5000 devices
1.
Temporarily wire the device to the MS/TP network and apply power. 
See “Wiring” on page  15.
2.
Start Envision for BACtalk.
3.
Open Device Manager and then perform a device scan. 
The unit will appear in the list of devices with device instance 9999 
(Model AZW-5000). 
4.
Save it to the table and then close Device Manager. 
5.
 Click the commissioning button you created. 
The device template opens. 
6.
Set the Extended PAN ID to a value other than the default (optional, but 
recommended). Remember to record the values.
7.
If the unit will function as a coordinator, set the Device Type to 0. If it 
will function as a transceiver or repeater, leave the default value (1).
N o t e
You can have only one coordinator per network.
C A U T I O N
Connecting more than one coordinator to a ZigBee 
network will cause routing loops and degrade performance.