Commissioning
 © Honeywell 
LTBT-TM-AZWIOG
Rev. 0001BETA
  
13
 
8.
Set the Device Instance.
9.
Set the ZigBee Network Number. You can use the default setting as 
long as it is unique across the BAS. All AZW-5000 devices on a given 
network must have the same ZigBee Network Number.
N o t e
You can set up overlapping ZigBee networks as long as you keep 
the ZigBee Network Numbers distinct.
10.
Set the MS/TP Network Number. This network number must be unique 
within the ZigBee network.
N o t e
Because each transceiver/controller pair form their own MS/TP 
network, the MS/TP Network Number for the coordinator must be 
different from the MS/TP Network Numbers of the transceivers.
11.
If you are commissioning a coordinator, leave the default Baud rate 
setting (0=Auto-baud). If you want to specify a Baud rate for a 
transceiver, type a rate.
12.
Click Commit Configuration Changes and then cycle power to the 
device.
N o t e
The display button will no longer open this unit because the 
device instance has changed. See “Viewing commissioning data” on 
page  21 for i
nstructions on accessing this data.
13.
If it is not functioning properly, see “Troubleshooting weak reception” 
on page  22
14.
Repeat steps 1 through 13 for each device. You can reuse the 
commissioning button because the units ship from the factory with the 
device instance set to 9999.