HID Global Corporation 607X Manuale Utente

Pagina di 8
6075-900, B.2 – FlexSmart™ 607X Series Installation Guide 
 
The following are recommended cable types and maximum cable lengths for a cable connecting the power supply 
to the reader. 
Cable Type 
Maximum Cable Length 
24 AWG (0.60mm), three conductors, with an overall foil shield, 9533 or 
equivalent. 
200’ (61 m) 
22 AWG (0.80mm), two conductors, with an overall foil shield, Alpha 5192 
or equivalent. 
300’ (91 m) 
18 AWG (1.20mm), two conductors, with an overall foil shield, 5836 or 
equivalent.  
500’ (152 m) 
The following are recommended wiring types at various maximum distances. Variations in distances 
require different wire gauges, because of system data termination differences. Contact your system 
manufacturer for its exact requirements. Installation should be in accordance with National Electric Code 
ANSI/NFPA 70. 
Cable Type 
Maximum Cable Length 
22 AWG (0.80mm), six or eight conductor, with an overall foil shield, Alpha 
5196, 5198 or equivalent.  
500’(152 m) 
18 AWG (1.20mm), six or eight conductor, with an overall foil shield, Alpha 
5386, 5388 or equivalent. 
500’ (152m) 
3.2  Grounding 
Connect the reader directly to an earth ground (an earth ground can be established by driving a copper 
clad ground rod into the earth). Make certain the DC resistance between your established earth ground 
and the system ground is 50 Ohms or less. If a direct connection to a ground rod is not possible, connect 
the reader to an earth grounded cold water metal pipe (do not connect to a copper fire sprinkler system 
because it may have non-conductive couplings) 
or steel frames (building beams) that connect to earth. 
Connection of the shield/drain to an earth ground will provide greater ESD protection of the reader.  
Prevent ground loops by connecting both the cable shield and the negative line of the power supply to one 
common earth ground point. Connecting different points to separate earth grounds may result in a ground 
loop.  
Note: For the heavy duty keypad readers, the Shield/drain wire should be floating at the power supply. 
Note: Ground loops may cause poor read range and communication line interference, resulting in no code 
or improper code seen by the controller. 
Reader Defaults 
 
Reader Wiring 
 
Card read (LED, beep & backlight) 
 
Red 
+12Vdc 
One-line control (bi-colour LED) 
 
Black 
0Vdc 
Keypad Defaults 
 
Green 
Data 0/Strobe 
Key-press (LED, beep & backlight) 
 
White 
Data 1/Data 
1 0001 
2 0010 
3 0011 
 
Brown 
LED Control 
4 0100 
5 0101 
6 0110 
 
Blue 
Beeper Control 
7 0111 
8 1000 
9 1001 
 
Orange 
Not Used 
Θ1010 
0 0000 
# 1011 
 
Shield/drain 
Door controller earth ground 
 
Page 6 of 8 
 
February 5, 2007 
© 2007 HID Global Corporation.  All rights reserved.