WIRELESS THERMOSTAT
69-1535
10
TROUBLESHOOTING GUIDE
For troubleshooting, see Table 6.
Table 6. Troubleshooting Guide.
Symptom
Possible Cause
Action
Display does not 
come on.
Thermostat is not being 
powered.
Check if batteries are present and installed correctly.
If batteries are present and installed correctly, replace thermo-
stat.
Temperature 
display is 
incorrect.
Room temperature display 
has been reconfigured.
Enter Installer Setup number 37 and reconfigure the display.
Thermostat is configured 
for °F or °C display.
Enter Installer Setup number 14 and reconfigure the display.
Poor choice of thermostat 
location.
Relocate the thermostat.
Temperature 
settings do not 
change. 
(Example: 
Cannot set the 
heating higher or 
the cooling 
lower.)
The upper or lower 
temperature limits were 
reached. 
Check the temperature setpoints:
•Heating limits are 40 to 90°F (4.5 to 32°C)
•Cooling limits are 48 to 99°F (7 to 35°C) 
The setpoint temperature 
range stops were 
configured.
Check Installer Setup numbers 34 and 35 and reconfigure the setpoint 
stops.
Heating does not 
come on.
Thermostat is calling for 
heat (flame icon is in 
display).
Troubleshoot the W8665 Receiver Module.
Troubleshoot the heating equipment.
Thermostat is not calling 
for heat (no flame icon is in 
display).
Raise heating setpoint above room temperature.
Check if the W8665 is set up to receive signals from this thermostat.
Set up W8665 to receive signals.
Thermostat minimum off 
time is activated.
Wait up to five minutes for the system to respond.
System selection is not set 
to Heat.
Set system selection to Heat.
Heating setpoint is below 
room temperature.
Check heating setpoint. Set heating setpoint to desired temperature.
Cooling does not 
come on.
Thermostat minimum off 
time is activated.
Wait up to five minutes for the system to respond.
Enter Installer Setup number 33. Reconfigure minimum off time (if 
required).
System selection is not set 
to Cool.
Set system selection to Cool.
Cool setpoint is above 
room temperature.
Check cooling setpoint. Set cooling setpoint to desired temperature.
Thermostat is calling for 
cool (snowflake is in 
display).
Troubleshoot cooling equipment.
Troubleshoot W8665 Receiver Module.
Thermostat is not calling 
for cool (no snowflake icon 
is in display).
Check if the W8665 is set up to receive signals from the thermostat.
Set up W8665 to receive signals.
System on 
indicator
(  
 = heat,
 
  = cool) is 
displayed, but no 
warm or cool air 
is coming from 
the registers.
Fan operation set for 0 
(conventional heat) when it 
should be set for 1 (electric 
heat).
Enter Installer Setup number 2 and reconfigure the fan operation.
Conventional heating 
equipment turns on the fan 
when the furnace has 
warmed up to a setpoint.
Wait a minute after seeing the on indicator and then check the 
registers.
Heating or cooling 
equipment is not operating.
Verify operation of heating or cooling equipment in self-test.
Thermostat 
backlight 
appears dim.
Backlight may fade over 
the life of the batteries.
Wait unit Replace Battery indicator is illuminated and replace 
batteries.
Replace batteries now.