Indicator Light
Pulsing: Normal/Thermal Alarm
Fast Blink: Smoke Alarm
None: Call for Service
Test Switch
S0162-00
Figure 1. 5808LST Wireless Smoke/Heat Detector
PROGRAMMING
The smoke detector’s ID must be enrolled in the control panel during installa-
tion of the system. The 5808LST must be enrolled on loop 1 as an input “Type 
3” (supervised RF).
With the control panel in the programming mode, enter the 7 digit serial number 
that is on the label of the 5808LST. For confirmation, press the test switch to 
send a transmission to the control panel.
See the control unit’s installation instructions for further details.
SMOKE DETECTOR LIMITATIONS
•  Smoke detectors will not sense a fire if the smoke does not reach the 
sensor  or  if  the  air  temperature  does  not  reach  135°  F.  In  order  for  a 
smoke detector to sense smoke, it must be installed in the immediate vicin-
ity of the fire. In addition, smoke from fires in chimneys, in walls, on roofs, 
in  remote  parts  of  the  building,  or  on  another  level  from  where  the  smoke 
detector  is  located,  may  not  reach  the  smoke  detector  quickly  enough  for 
occupants  to  escape  unharmed. 
For  this  reason,  installer  shall  install 
smoke  detectors  on  every  level,  in  every  sleeping  area,  and  in  every 
bedroom of the household. 
•  Smoke detectors may not be heard. The alarm horn in this smoke detector 
meets or exceeds current Underwriter’s Laboratories standards. However, if 
the  smoke  detector  is  not  located  in  the  same  room  as  the  occupant,  or  if 
it  is  blocked  by  a  closed  door  or  normal  noise,  the  alarm  horn  may  not  be 
heard. In addition, sound sleepers, or persons who are under the influence of 
drugs or alcohol may not hear the alarm or be able to react to it. 
Therefore, 
locate this smoke detector, which has a sounder rated at 85 dB at 10 
feet, on every level, in every sleeping area, and in every bedroom of the 
household.
•  In general, detectors may not always warn you about fires caused by care-
lessness and safety hazards like smoking in bed, violent explosions, escaping 
gas, improper storage of flammable materials, overloaded electrical circuits, 
children playing with matches, or arson.
•  Smoke  detectors  are  not  fool-proof. 
Like  all  electronic  devices,  smoke 
detectors have limitations. No type of smoke detector can sense every 
kind of fire every time. In addition, smoke from slow, smoldering fires 
rises slowly and may not reach the smoke detector until actual flame 
breaks  out.  This  type  of  smoke  may  not  reach  the  smoke  detector  in 
time for occupants to escape unharmed.
•  Smoke  detectors  are  not  a  substitute  for  life  or  property  insurance. 
Though smoke detectors have been responsible for saving many lives, they 
are not warranted or implied to protect lives or property in the event of a fire.
Before  installing  detectors,  please  thoroughly  read  these  installation  instruc-
tions and Manual I56-407, Guide for Proper Use of System Smoke Detectors, 
which  provides  detailed  information  on  detector  spacing,  placement,  zoning, 
wiring,  and  special  applications.  Copies  of  this  manual  are  available  from 
ADEMCO.
NOTICE: This manual should be left with the owner/user of this equipment.
I
MPORTANT: This detector must be tested and maintained regularly following 
NFPA 72 requirements. The detector should be cleaned at least once a year.
GENERAL DESCRIPTION
The 5808LST photoelectronic smoke/heat detector with built-in wireless trans-
mitter is intended for use with wireless alarm systems that support 5800 series 
devices. Refer to control/communicator installation instructions for compatibil-
ity. The 5808LST smoke/heat detector can be used with 5881 series (L, M, H) 
and 5881EH receivers for residential installations. For commercial installations, 
the 5881EH receiver should be used. The transmitter can send alarm, tamper, 
maintenance  (when  control  panels  are  equipped  to  process  maintenance 
signals), and battery condition messages to the system’s receiver. The main-
tenance signal fully complies with the sensitivity test requirement specified in 
NFPA 72, 7-2.2. Refer to the wireless system’s instructions for the maximum 
number of transmitters that can be supported.
The  5808LST  will  sound  its  built-in  temporal  horn  when  smoke  activates  the 
detector  (also  the  LED  also  flashes  rapidly),  or  when  the  air  temperature 
reaches  135°  F  (the  LED  flashes  normally,  about  once  every  40  seconds). A 
message is also sent to the wireless control panel and the smoke detector’s ID 
number is displayed at the console. The alarm message is transmitted every 4 
seconds until the smoke condition has cleared and the detector has reset. After 
the horn stops, a RESTORE message is transmitted to the control panel and the 
ID number can be cleared from the panel. During normal and low battery condi-
tions, the LED flashes approximately once every 40 seconds. The built-in Drift 
Compensation algorithm automatically maintains the sensitivity of the detector. 
Once the detector reaches its limit of compensation, it transmits a maintenance 
signal to the panel. In maintenance condition, the LED stops flashing.
BATTERY INSTALLATION AND REPLACEMENT
The 5808LST is powered by two 3-volt CR123A or DL123A Lithium batteries 
(included). The detector checks for low batteries at least every 60 minutes. If 
a low battery is detected, the transmitter sends a low battery message to the 
control panel, which beeps and displays the detector’s ID. This condition will 
exist  for  a  minimum  of  seven  days,  and  then  the  detector’s  horn  will  “chirp” 
about every 40 seconds. The batteries should be replaced BEFORE the chirps 
begin. Be sure to replace BOTH batteries with fresh ones. 
To replace batteries:
1.  Remove the detector from its mounting plate by twisting the detector coun-
terclockwise. Remove batteries, and dispose properly.
2.  Install two new 3-volt CR123A Lithium batteries in the battery compartment. 
Follow the polarity diagram inside the compartment.
3.  Reinstall the smoke detector onto the mounting plate by turning the detec-
tor clockwise.
4.  Test  the  detector  as  described  in  the TESTING TRANSMITTER  SIGNAL 
section of this manual. The LED should flash about once every 40 seconds 
to indicate normal operation. If the batteries are not installed correctly, the 
smoke detector will not operate and the batteries may be damaged. If the 
detector  does  not  appear  to  be  sending  a  signal  during  any  of  the  tests, 
check for correct battery installation.
AD300-00-00 
I56-918-14R
Honeywell, 165 Eileen Way, Syosset, New York 11791
5808LST Photoelectronic Smoke/Heat Detector with 
Built-in Wireless Transmitter Installation Instructions
SPECIFICATIONS
Power Source: 
 Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo CR123A, Panasonic CR123A 
or ADEMCO 466.)
Height: 
2.05 inches (52 mm)
Diameter: 
5.0 inches (127 mm) without adapter bracket
 
5.5 inches (140 mm) with adapter bracket
Weight: 
8.5 oz. (241 g) without batteries
Operating Ambient Temperature Range: 
0° to 38° C (32° to 100° F)
Operating Humidity Range: 
5% to 95% Relative Humidity
Heat Sensor: 
135° F Fixed Temperature Electronic Thermistors 
Agency Listings: 
UL 268 – Commercial and Residential Installations
®