Honeywell International Inc. 8DL5809EN Manuale Utente
K9948 4/04 Rev. A
ADEMCO 5809EN
Rate-Of-Rise Heat Detector
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 5809EN Rate-of-Rise Heat Detector is a
wireless device used with ADEMCO alarms systems that
support 5800 series devices.
wireless device used with ADEMCO alarms systems that
support 5800 series devices.
The 5809EN combines both rate-of-rise and fixed
temperature sensors. Fires typically cause a rapid rise in
temperature in the surrounding area. The 5809EN’s rate-
of-rise thermostat senses the rise in temperature and
signals an alarm if the rise is 15
temperature sensors. Fires typically cause a rapid rise in
temperature in the surrounding area. The 5809EN’s rate-
of-rise thermostat senses the rise in temperature and
signals an alarm if the rise is 15
°F (8°C) or more per
minute. A built-in fixed temperature sensor will also signal
an alarm if the ambient temperature rises above 135
an alarm if the ambient temperature rises above 135
°F
(57
°C).
NOTE: If the fixed temperature sensor activates, the
5809EN must be replaced.
5809EN must be replaced.
The 5809EN is powered by a 3-volt lithium battery. If the
battery voltage gets too low, the 5809EN sends a low
battery signal to the control panel.
battery voltage gets too low, the 5809EN sends a low
battery signal to the control panel.
The 5809EN also features a tamper switch, which causes a
trouble signal to be sent to the control if the unit is removed
from the mounting base.
trouble signal to be sent to the control if the unit is removed
from the mounting base.
A built-in activation button, located on the detector
assembly, is used when programming the unit’s serial
number at the control and when testing the unit.
assembly, is used when programming the unit’s serial
number at the control and when testing the unit.
Installing the Battery
Important Notes:
• Use 3-volt lithium battery:
Important Notes:
• Use 3-volt lithium battery:
Duracell DL 123A or
Panasonic/Sanyo/Varta CR123A.
Panasonic/Sanyo/Varta CR123A.
• Observe polarity.
• When replacing the battery, wait at least 30 seconds
• When replacing the battery, wait at least 30 seconds
after removing the old battery, before installing the new
one.
one.
Remove the detector assembly from its mounting base and
install a 3-volt lithium battery as shown below.
install a 3-volt lithium battery as shown below.
BATTERY
5809EN-003-V0
PROGRAMMING THE UNIT
The transmitter’s serial number must be enrolled in the
control panel before usage in the system. Refer to the
Installation and Setup Guide for which this device is to be
used for programming procedures for enrolling transmitter
serial numbers. Before programming do the following:
control panel before usage in the system. Refer to the
Installation and Setup Guide for which this device is to be
used for programming procedures for enrolling transmitter
serial numbers. Before programming do the following:
1. Remove the unit assembly from its mounting base by
twisting counter-clockwise and lifting.
2. Install the battery (if not already installed). Observe
polarity!
3. Enter the control’s programming mode and follow the
control’s programming instructions. When
programming this transmitter at the control, note the
following:
programming this transmitter at the control, note the
following:
• Input Type = 3 (Supervised RF)
• Loop number = 1
Transmit from the detector when prompted (momentarily
press the activation button in shown below). You can also
manually enter the detector’s serial number.
• Loop number = 1
Transmit from the detector when prompted (momentarily
press the activation button in shown below). You can also
manually enter the detector’s serial number.
4. Test the detector after enrolling into the system. Refer
to the Testing section.
5809EN-001-V0
ACTIVATION
BUTTON
TAMPER
SWITCH
MOUNTING THE DETECTOR
You can mount the 5809EN on a wall or ceiling within the
protection area:
• Wall Mounting: Mount the detector 4” - 6” from the
protection area:
• Wall Mounting: Mount the detector 4” - 6” from the
ceiling.
• Ceiling Mounting: Mount the detector at least 4” from
any wall. Make sure the normal ceiling temperature
will not exceed 100
will not exceed 100
°F.
• Refer to NFPA Standard 72 for detector spacing and
other requirements. Maximum spacing for UL
installations is 50’x50’.
installations is 50’x50’.
• Avoid mounting the detector near heat generating
devices (e.g. ovens, heat vents, furnaces, boilers).
IMPORTANT: Heat detectors should be used for property
protection. Reliance should not be placed
solely on heat detectors for life safety.
When life safety is involved, smoke
detectors MUST also be used. Detectors
must not be painted.
solely on heat detectors for life safety.
When life safety is involved, smoke
detectors MUST also be used. Detectors
must not be painted.
Wireless Transmission Path Test
A good RF transmission path must be established from the
proposed mounting location before permanently installing
the detector. To determine that there is good signal
reception from the proposed location, perform the test
procedure described in TESTING THE DETECTOR section.
A good RF transmission path must be established from the
proposed mounting location before permanently installing
the detector. To determine that there is good signal
reception from the proposed location, perform the test
procedure described in TESTING THE DETECTOR section.
Once a good RF transmission path is confirmed, mount the
detector as follows:
detector as follows:
DRAFT COPY 4/27/04
RevB