Honeywell International Inc. 8DL5809EN Manuale Utente

Pagina di 2
K9948  4/04  Rev. A 
 
 
ADEMCO 5809EN 
Rate-Of-Rise Heat Detector 
INSTALLATION AND SETUP GUIDE 
GENERAL INFORMATION 
The ADEMCO 5809EN Rate-of-Rise Heat Detector is a 
wireless device used with ADEMCO alarms systems that 
support 5800 series devices.     
The 5809EN combines both rate-of-rise and fixed 
temperature sensors.  Fires typically cause a rapid rise in 
temperature in the surrounding area.  The 5809EN’s rate-
of-rise thermostat senses the rise in temperature and 
signals an alarm if the rise is 15
°F (8°C) or more per 
minute.  A built-in fixed temperature sensor will also signal 
an alarm if the ambient temperature rises above 135
°F 
(57
°C).   
NOTE:  If the fixed temperature sensor activates, the 
5809EN must be replaced.   
The 5809EN is powered by a 3-volt lithium battery.  If the 
battery voltage gets too low, the 5809EN sends a low 
battery signal to the control panel.   
The 5809EN also features a tamper switch, which causes a 
trouble signal to be sent to the control if the unit is removed 
from the mounting base.   
A built-in activation button, located on the detector 
assembly, is used when programming the unit’s serial 
number at the control and when testing the unit.   
Installing the Battery 
Important Notes:   
•  Use 3-volt lithium battery:   
Duracell DL 123A or  
Panasonic/Sanyo/Varta CR123A.   
•  Observe polarity.   
•  When replacing the battery, wait at least 30 seconds 
after removing the old battery, before installing the new 
one.   
Remove the detector assembly from its mounting base and 
install a 3-volt lithium battery as shown below.   
BATTERY
5809EN-003-V0
 
PROGRAMMING THE UNIT 
The transmitter’s serial number must be enrolled in the 
control panel before usage in the system.  Refer to the 
Installation and Setup Guide for which this device is to be 
used for programming procedures for enrolling transmitter 
serial numbers.  Before programming do the following:   
1.  Remove the unit assembly from its mounting base by 
twisting counter-clockwise and lifting.   
2.  Install the battery (if not already installed).  Observe 
polarity!   
3.  Enter the control’s programming mode and follow the 
control’s programming instructions.  When 
programming this transmitter at the control, note the 
following:   
•  Input Type = 3 (Supervised RF) 
•  Loop number = 1 
Transmit from the detector when prompted (momentarily 
press the activation button in shown below).  You can also 
manually enter the detector’s serial number.   
4.  Test the detector after enrolling into the system.  Refer 
to the Testing section.   
5809EN-001-V0
ACTIVATION
BUTTON
TAMPER
SWITCH
 
MOUNTING THE DETECTOR 
You can mount the 5809EN on a wall or ceiling within the 
protection area:   
•  Wall Mounting:  Mount the detector 4” - 6” from the 
ceiling.   
•  Ceiling Mounting:  Mount the detector at least 4” from 
any wall.  Make sure the normal ceiling temperature 
will not exceed 100
°F.   
•  Refer to NFPA Standard 72 for detector spacing and 
other requirements.  Maximum spacing for UL 
installations is 50’x50’.   
•  Avoid mounting the detector near heat generating 
devices (e.g. ovens, heat vents, furnaces, boilers).   
IMPORTANT:  Heat detectors should be used for property 
protection.  Reliance should not be placed 
solely on heat detectors for life safety.  
When life safety is involved, smoke 
detectors MUST also be used.  Detectors 
must not be painted.   
Wireless Transmission Path Test 
A good RF transmission path must be established from the 
proposed mounting location before permanently installing 
the detector.  To determine that there is good signal 
reception from the proposed location, perform the test 
procedure described in TESTING THE DETECTOR section.   
Once a good RF transmission path is confirmed, mount the 
detector as follows:   
DRAFT COPY 4/27/04 
RevB