Honeywell International Inc. 8DL5882-4 Manuale Utente

Pagina di 8
 
b.  Verify that DIP switch #1 is in the OFF position. 
c.  Set DIP switch #5 according to the following chart. 
DIP SWITCH #5 
For . . . 
Set to . . . 
Commercial Fire Applications 
ON 
Non-commercial Fire Applications 
OFF 
NOTES: 
  If multiple receivers are used on one control, DIP 
switch #5 must be set to the same position on all 
receivers. 
 
DIP switch #5 reduces sensitivity during 
supervision message reception. For commercial fire 
applications, DIP switch #5 must  be  in  the  ON 
position. 
5.  Insert the wiring plug (with 4 flying leads) into the 
mating socket on the receiver (see Figure 3 for socket 
location). Connect the  4 wires to the control's 
corresponding keypad terminals (see “Interface Wiring” 
in the SPECIFICATIONS section). 
6. Install the antennas in the right-hand terminals of the 
two terminal blocks at the upper edge of the circuit 
board, one into each block’s right-hand terminal, and 
tighten the screws to secure them.  
 
Caution: Avoid mounting the receiver antennas against 
a metal surface. 
7.  Proceed with any programming of the control that 
may be necessary for RF operation, and the 
installation of the system's wireless transmitters, 
as described in the control's installation and setup guide 
and the transmitter's installation instructions. 
 
NOTES: 
  The receiver can support up to 16 encrypted wireless 
transmitters (keys). The total quantity of wireless 
keys (encrypted and unencrypted) that can be used is 
determined by the control panel. 
  Wireless key buttons must be enrolled to zones in the 
control panel via zone programming first. If the 
wireless  key  is  to  be  used  for  arming  and  disarming 
the VISTA-40 and up, a user number must then be 
assigned to the wireless key via user programming. If 
it is not done in this order, you will be unable to 
respond successfully to the RF button zone number 
prompt in user programming. 
  If more than one receiver is being used and you are 
using encrypted wireless keys, we recommend that 
you (a) enter the GO/NO GO mode, (b) disconnect one 
receiver, (c) enroll all encrypted keys into the 
connected receiver, (d) reconnect the disconnected 
receiver, (e) exit the GO/NO GO mode, and then (f) 
repeat (a) through (e) for the receiver that was 
disconnected.  
  The RED LED located on the receiver's circuit board 
should be used as an indicator of strong local radio 
frequency interference. If this LED is continuously 
illuminated, the receiver should be relocated. 
  After a successful enrollment of an encrypted key, the 
GREEN LED blinks the number of spaces that are 
free for additional encrypted key enrollment. 
8.  Replace the receiver's cover. 
ENCRYPTED KEYS 
The receiver can support up to 16 encrypted wireless 
transmitters (keys) at one time. If the number on the 
receiver microprocessor is WAK 4406-4 or higher, the 
receiver provides you with the capability to check space 
available and/or delete encrypted keys using the procedures 
below. 
The GREEN LED located on the receiver's circuit board 
may be used to determine how many more encrypted keys 
may be enrolled into the receiver. This LED is also used to 
indicate when encrypted keys may be deleted. To determine 
how many more encrypted keys may be enrolled and/or to 
delete enrolled encrypted keys: 
1. Remove power from the receiver and set DIP 
switch 1 to the ON position. 
2.  Apply power to the receiver and watch the GREEN 
LED. You will see one of the following indications: 
a.  The GREEN LED blinks the number of spaces that 
are free for additional encrypted key enrollment and 
then goes to constantly ON. 
b. The GREEN LED is constantly ON, indicating the 
receiver is full. 
c.  The GREEN LED is OFF, indicating no encrypted 
keys are enrolled. 
3. If you do not want to delete any enrolled 
encrypted keys, advance to step 4. If you want to 
delete enrolled encrypted keys, wait until the 
GREEN LED is constantly ON in step 2 a. or 2 b. 
above and then: 
a. Record the positions of DIP switches 1 through 
5. 
b. Set DIP switches 1 through 5 to the opposite 
positions of their current settings and wait a 
few moments. 
c. Set DIP switches 1 through 5 back to their 
original positions as recorded in step a. All 
enrolled encrypted keys will be deleted. 
4.  Place DIP switch 1 back into the OFF position to 
return to normal receiver operation.