  AL-111X Arming Station
Keyboard Backlight and Night Light
The default keyboard backlight and night light settings are as follows:
Keyboard backlight on (bright) for approximately 4 1/4 minutes following a key press.
Night light on (dim).
These functions can be changed from the RAS menu. See Menu Options.
LCD Contrast
The LCD contrast may be adjusted by pressing and holding
the [*MENU] key while momemtarily pressing the [UP] or
[DOWN] keys to change the display contrast. The default
setting is 12.
LCD Backlight
The LCD backlight illuminates for 30 seconds following a key press.
Beeper Tone
The beeper tone may be adjusted by pressing and holding the [CLEAR] key while momentarily pressing the [UP] or
[DOWN] keys to change the beeper tone. The default setting is 16.
LCD Text Format
AL- 1111 and AL-1116 RAS have a 4 line x 16 character LCD and may display text in the following three alternative
formats:
Format 1 (default) wraps text using hyphens when a word is broken onto the next line.
Format 2 wraps text without hyphens when a word is broken onto the next line.
Format 3 wraps text to the next line without breaking words.
To change formats, press and hold the [0] (zero) key while momentarily pressing the [UP] or [DOWN] keys. This option is
not available on AL-1110 or AL-1115 RAS with 2 line x 16 character LCD.
Card Reader (AL-1115 and AL-1116 only)
AL-1115 and AL-1116 RAS are fitted with a Smart Card reader which uses the address of the RAS to communicate with
the panel and so does not need to have its own System BUS address.
The Smart Card reader is located behind the keypad with the number 2 key being the approximate center (see Figure 1). The
sensitivity of the reader is dependent on the environment on which it is mounted (large metal surfaces will reduce the
reader’s sensitivity).
Power Up
Upon initial power up, the beeper will sound two beeps indicating that the internal non-volatile memory is OK. All of the
area LEDs may illuminate, indicating that the system is armed. All area must be disarmed in order to enable access to the
installer programming menu options.
 Status LED Indications
AL-111X RAS have four status LEDs above the LCD panel (see Figure 1):
Power - The Green LED illuminates when the control panel is powered by the AC supply.
Fault - The Yellow LED illuminates to indicate detection of a system fault.
Access - The Blue LED flashes when access to an area assigned to the RAS is granted. It also flashes once when a
card is badged at an AL-1115 or AL-1116 (subject to Valid Card Flashing Programming).
Alarm - The Red LED illuminates when there is a system tamper or an area assigned to the RAS is in alarm state. The
area may be identified by viewing the 16 area LEDs visible when the RAS cover is open or removed.
 Area LED Indications
When the RAS cover is opened or removed, 16 red area LEDs are visible at the bottom of the RAS (see Figure 1). Each
LED represents an area, and the indications are as follows:
The LED illuminates when its corresponding area is armed.
The LED flashes slowly when a fault is detected in its corresponding area.
The LED flashes quickly when an alarm occurs in its corresponding area.
 Operating Features
UP Key
DOWN Key