Honeywell International Inc. WFSPS Manuale Utente

Pagina di 64
24
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
FWSG FlashScan Wireless System Gateway
Operations
7.
Click Collapse Mesh. The Collapse mesh network screen is displayed.
8.
Click Yes. The gateway password screen displays.
9.
Enter the verification password in the Gateway Password screen.
 
The network is now collapsed and a confirmation message is 
displayed as shown below. 
Collapse Mesh Network at the Panel
To collapse the mesh network using the NFS2-3030 or NCA-2 with NFS2-640 FACP, refer to the “shutdown wireless” section of the 
NFS2-3030 or NCA-2 Manual.
2.9.6  Silence Network Command
The silence network command is a diagnostic function to turn off all radio communication from the wireless devices for a set amount of 
time. All devices will retain the profile information but will be removed from the mesh. The devices will not send or receive any wireless 
communication until the set time expires or the device is rebooted. The mesh network can be reformed at the end of the silence period or 
after the device is restarted. 
The mesh network can be silenced using SWIFT Tools.The mesh network can also be silenced at the NFS2-3030 panel or NCA-2 when 
used as a primary display with the NFS2-640.
Silence Mesh Network Using SWIFT Tools
To silence the mesh network:
1.
Connect the W-USB adapter to your computer. For more information on the USB adapter, refer to Section 5.
2.
Launch the SWIFT Tools application. Refer to Appendix A, “SWIFT Tools” for more information.
3.
From the Home Screen, select the Diagnostics function.
4.
Select a Gateway from the communicator panel.
5.
Click View Mesh. The mesh is displayed.
co
lla
p
se
m
eshn
e
two
rk.
jp
g
Figure 2.22  Collapse Mesh Network Option
co
lla
p
se
m
eshn
e
two
rkco
nf
irm.jpg
Figure 2.23  Collapse Mesh Network Confirmation
!
CAUTION: FIRE PROTECTION DISABLED
FIRE PROTECTION FROM WIRELESS DEVICES WILL BE DISABLED WHEN A SILENCE COMMAND IS ISSUED.