Honeywell International Inc. WFSPS Manuale Utente

Pagina di 64
22
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
FWSG FlashScan Wireless System Gateway
Operations
5.
Select Gateway Operations to lock/unlock the gateway. The Lock/Unlock gateway screen appears, displaying the gateway that is 
locked. 
6.
Select desired gateway and click Lock or Unlock as required.
• Lock - The Lock Gateway screen is displayed. Create a password and click Lock. The gateway is locked.
• Unlock - The Enter password for Gateway screen is displayed. Enter the password and click Unlock. The gateway is 
unlocked.
Password Reset
To reset the password, contact technical support.
2.9.4  Weak Link Trouble Reporting
The SWIFT Network uses two paths of communication for each device. To establish the link between devices as a viable communication 
path, the signal strengths must meet the limits provided in Section 2.3. The SWIFT Network implements a higher threshold for primary 
connections to provide an extra layer of robustness and immunity from interference. A weak link trouble condition is initiated for any 
device that does not have at least one connection at the primary threshold. This is an optional setting that can be disabled to ignore the 
weak link trouble condition. The trouble can be disabled at the gateway or at the FACP (NFS2-3030 or NFS2-640 with NCA-2 only). 
Disabling the trouble reporting at the panel will prevent the event from registering as a trouble but still enters into history as a back-
ground event. Disabling the trouble reporting at the gateway prevents the event from being reported to the FACP as a trouble or a non-
trouble event. To enable trouble reporting, turn on the settings at both locations.
Disable Trouble Reporting at the Gateway Using SWIFT Tools
To disable trouble reporting at the gateway through SWIFT Tools:
1.
Connect the W-USB adapter to your computer. For more information on the USB adapter, refer to Section 5.
2.
Launch the SWIFT Tools application. Refer to Appendix A, “SWIFT Tools” for more information.
3.
From the Home Screen, select the Diagnostics function.
4.
Select the desired gateway from the communicator panel.
5.
Click View Mesh.
6.
Click Advanced Functions. A drop-down list is displayed.
lo
ck_
un
lco
k_g
ate
w
ay.p
ng
Figure 2.17  Lock/Unlock Screen
Figure 2.18  Communicator Panel
se
lco
mm.
pn
g
ad
vfu
n
cdro
p.wmf
Figure 2.19  Advanced Functions Options