Honeywell International Inc. WFSPS Manuale Utente

Pagina di 64
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
51
Conduct a Site Survey
Site Survey
B.1.3  Retrieving Site Survey Results
To retrieve the site survey results:
1.
Return the device to “Pending Site Survey” or “Factory Default” mode. This is done by tampering devices that have completed a 
link quality test or by rebooting devices that have completed an RF scan test.  
2.
Plug the USB adapter into the laptop/PC where SWIFT Tools has been installed.
3.
Bring the devices within a range of approximately 20 feet from the USB adapter connected to the laptop/PC.
4.
Logon to SWIFT Tools and retrieve the data.
!
CAUTION: SITE SURVEY RESULTS WILL BE REPLACED
DO NOT CLEAR THE TAMPER ON A DEVICE THAT IS IN THE “PENDING SITE SURVEY” STATE OR THE EXISTING 
RESULTS WILL BE REPLACED.