Appendix E: Firmware Upgrade/Downgrade Instructions
To ensure proper system operation, this product must be 
tested in accordance with NFPA 72 after any programming operation 
or change in 
site-specific software.
E.1  W-USB Adapter Upgrade Procedure
The following procedure provides firmware upgrade instructions for the W-USB adapter. Ensure the latest version of SWIFT Tools is 
installed. SWIFT Tools and firmware can be downloaded from www.esd.notifier.com. There are multiple .bin files with the zip file. Save 
the files to a folder.
1.
Insert the W-USB adapter into the PC.
2.
Launch SWIFT Tools and navigate to the home screen and select either Site Survey, Create Mesh Network, or Diagnostics.
3.
SWIFT Tools will detect the connected USB adapter and will show an incompatibility message.  Click on the OK button to dismiss 
the message.
4.
Click on the Operations icon and navigate to Operations > Firmware Update > USB Adapter.
5.
Click Browse and navigate to the folder with the saved firmware. Select the file named “USBAdaptorVx.xxx.bin”.
6.
Click Update. The progress status box will show “Updating,” followed by “Updated”.
7.
Once the firmware update process completes SWIFT tools displays a message indicating that the W-USB adapter has been 
successfully upgraded.
E.2  Gateway Firmware Upgrade/Downgrade Procedure
The following procedure provides firmware upgrade and download instructions for the gateway. Ensure the latest version of SWIFT 
Tools is installed. SWIFT Tools and firmware can be downloaded from www.esd.notifier.com. There are multiple .bin files with the zip 
file. Save the files to a folder.
1.
Launch SWIFT Tools and navigate to the home screen and select either Site Survey, Create Mesh Network, or Diagnostics.
2.
Ensure gateway is in range of W-USB adapter and the PC running SWIFT Tools.
3.
Click on the Extras icon and navigate to Extras > Firmware Update > Wireless Devices.
4.
Go to the Gateway area of the upgrade.
The gateway has two microprocessors that need to be upgraded. 
5.
Under “Select RF app update file”, click on the Browse button.
6.
Navigate to the folder with the saved firmware. Select the “WSG_RF_xx.xx.xx.bin” file.
7.
Select the gateway and click the Update button on the bottom of the screen. 
8.
Follow the window prompts. The download should take approximately 4 minutes to complete.
9.
Click the refresh button at the bottom of the window and Remove before starting the next download.
Repeat the same steps for the SLC app file.
10. Under the “Select SLC app update file”, click on the Browse button.
11. Navigate to the folder with the saved firmware. Select the “WSG_SLC_xx.xx.xx.bin” file.