SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
Firmware Upgrade/Downgrade Instructions
Device Firmware Upgrade/Downgrade Procedure
12. Select the gateway and click the Update button on the bottom of the screen. 
13. Follow the window prompts. The download should take approximately 4 minutes to complete.
E.3  Device Firmware Upgrade/Downgrade Procedure
The following procedure provides firmware upgrade and download instructions for the wireless devices. Ensure the latest version of 
SWIFT Tools is installed. SWIFT Tools and firmware can be downloaded from www.esd.notifier.com. There are multiple .bin files with 
the zip file. Save the files to a folder.
1.
If the device is current in a mesh network, power down the gateway. Devices can only be updated when they are in direct 
communication with SWIFT Tools.   
2.
Launch SWIFT Tools and navigate to the home screen and select either Site Survey, Create Mesh Network, or Diagnostics.
3.
Ensure devices are in range of W-USB adapter and the PC running SWIFT Tools.
4.
Click on the Extras icon and navigate Extras > Firmware Update > Wireless Devices.
5.
Go to the Detectors and Modules area of the upgrade.
6.
Under “Select the update file”, click on the Browse button.
7.
Navigate to the folder with the saved firmware. Select the “WDV_RF_xx.xx.xx.bin” file. The application file for a device is the 
same for all detector types and module types. 
8.
Select the devices and click the Update button on the bottom of the screen. Only permitted devices with a matching hardware 
revision and device type will be selectable. Multiple devices can be selected, and they will be updated sequentially.
9.
Follow the window prompts. The download should take approximately 4 minutes to complete.
10. Repeat until all devices in the mesh are operating with the same firmware version.