SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C 5/8/2015
FWSG FlashScan Wireless System Gateway
Operations
Activating the Profile Magnetic Sensor
Activating the profile magnetic sensor (refer to Figure 2.2) when the gateway has a profile will put 
the gateway in a mode of distributing the profile to any device that requests a profile. The gate-
way’s LED pattern will be altered when it is distributing a profile for easy identification. Profile 
distribution will automatically terminate after 10 minutes. For more information on gateway LED 
patterns, refer to Section 2.5 on page 12. 
2.8.4  SLC Configuration
The gateway:
communicates with the control panel via the SLC. 
is a FlashScan-only device. 
does not support CLIP mode.
is only compatible with FACPs version 24 or higher.
occupies one module SLC address. Set the address using the rotary dials on the gateway 
prior to installation. 
The SLC point uses the following configuration parameters:
Module Type: Monitor
Type Code Label: RF GATEWAY
FlashScan Type: RF GATEWAY
A gateway does not initiate alarms but the point is used for event reporting.
2.9  Operations
2.9.1  Modes of Operation
TENS
8 9
10
11
12
13
14
15
0
1
2
3
4
5
6 7
ONES
8 9
0
1
2
3
4
5
6 7
Figure 2.14  Address Rotary Switches
SL
C-se
tad
d
tp
h.
w
m
f
Figure 2.15  Gateway Modes Of Operation
op
mo
de
s.w
m
f
Start-up
Factory 
Default
Profile 
Configured
Mesh 
Formation
Initial Mesh 
Restructuring
Normal 
Mode
Mesh 
Restructuring
Rescue 
Mode
Fire Protection Provided