SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C 5/8/2015
FWSG FlashScan Wireless System Gateway
Operations
Activating the Profile Magnetic Sensor
Activating the profile magnetic sensor (refer to Figure 2.2) when the gateway has a profile will put
the gateway in a mode of distributing the profile to any device that requests a profile. The gate-
way’s LED pattern will be altered when it is distributing a profile for easy identification. Profile
distribution will automatically terminate after 10 minutes. For more information on gateway LED
patterns, refer to Section 2.5 on page 12.
the gateway in a mode of distributing the profile to any device that requests a profile. The gate-
way’s LED pattern will be altered when it is distributing a profile for easy identification. Profile
distribution will automatically terminate after 10 minutes. For more information on gateway LED
patterns, refer to Section 2.5 on page 12.
2.8.4 SLC Configuration
The gateway:
communicates with the control panel via the SLC.
is a FlashScan-only device.
does not support CLIP mode.
is only compatible with FACPs version 24 or higher.
occupies one module SLC address. Set the address using the rotary dials on the gateway
prior to installation.
prior to installation.
The SLC point uses the following configuration parameters:
•
Module Type: Monitor
•
Type Code Label: RF GATEWAY
•
FlashScan Type: RF GATEWAY
A gateway does not initiate alarms but the point is used for event reporting.
2.9 Operations
2.9.1 Modes of Operation
TENS
8 9
10
11
12
13
14
15
0
1
2
3
4
5
6 7
ONES
8 9
0
1
2
3
4
5
6 7
Figure 2.14 Address Rotary Switches
SL
C-se
tad
d
tp
h.
w
m
f
Figure 2.15 Gateway Modes Of Operation
op
mo
de
s.w
m
f
Start-up
Factory
Default
Profile
Configured
Mesh
Formation
Initial Mesh
Restructuring
Normal
Mode
Mesh
Restructuring
Rescue
Mode
Fire Protection Provided