15
Mounting & Wiring
FWSG
2.5.3  FWSG Powered from SLC
To power the FWSG using the signal line circuit, connect it as described in table 2.1 below:
Figure 2.5  Wiring Connections (FWSG powered from SLC)
NOTE: It is recommended to use the same wire gauge if there are multiple connections to the 
same terminal.
The FWSG provides isolation of short circuits on the SLC in Class A installations, that use the A6 
and A7 connections as an in and out connection. A5 is common for SLC wiring that enters and 
leaves. Class B wiring that terminates at the FWSG can use either the A6 or A7 connection for the 
SLC positive.  SLC connections are power limited by the panel.  An interruption in the SLC that 
causes a loss of power at the FWSG for more than 100ms may result in a trouble condition and loss 
of fire protection provided by the wireless devices for up to 15 minutes. Using an external 24V 
power source (not SLC power) is recommended for installations that require fire protection in the 
presence of short circuits, including class A applications and applications that utilize isolator mod-
ules.
Terminal Pins
Description 
A5 & A7
SLC Common & SLC Output/Input
A5 & A6
SLC Common & SLC Input/Output
A4 & A5
Jumper selection to enable power from the SLC supply (Insert jumper when 
using SLC power)
A3
Unused
A1 & A2
Jumper selection to disable power from the external supply. (Insert jumper 
when using SLC power) 
Table 2.1