Honeywell International Inc. WFSSD Manuale Utente

Pagina di 74
16
PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0  10/10/2013
FWSG
Mounting & Wiring
2.5.4  FWSG Powered from an External +24VDC Source
To power the FWSG using a +24VDC source, connect the FWSG as described in table 2.2 below. 
Figure 2.6  Wiring Connections -FWSG powered from an external +24VDC source
NOTE: Terminal A5 is referenced more than once in the above connections. It is recommended 
to use wire of the same gauge for all connections to A5 and use the same wire gauge if there are 
multiple connections to the same terminal.
The FWSG provides isolation of short circuits of the SLC in class A installations that use the 
A6and A7 as an in and out connection. A5 is common for in and out SLC wiring. Class B SLC wir-
ing that terminates at the FWSG can use either the A6 or A7 connection for the SLC positive. SLC 
connections are power limited by the panel. 24VDC must be power limited by the source.
Terminal Pins
Devices Powered
A5 & A7
SLC Input/output
A5 & A6
SLC Input/output
A4
Unused
A2 & A3
+24VDC input. Voltage range from 18VDC to 30VDC. Use only power 
limited circuits
A1
Unused
Table 2.2