PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0  10/10/2013
FWSG
Configuration and Programming
4. Activate either magnetic sensor with a magnet within ten seconds of starting up the FWSG 
while the double red blink is active on the FWSG.  (If you miss this ten-second window, power 
down the FWSG and repeat step 1).  The LED next to the magnetic sensor emits a red light for 
one second when it is activated.
When the profile is successfully created, the LEDs on the FWSG emit green light for five seconds   
(Refer to 2.7.2 "Magnet Sensor Activations" for further information on activating magnetic sen-
sors). A default profile has been created, containing a mesh ID, and a password. The default pass-
word is ‘12345’ and is needed if the FWSG is locked by the FACP and later accessed by the PC-
based configuration tool.
Next, the FWSG starts the profile distribution mode. Refer to 2.6.3 "Profile Distribution" for fur-
ther information on profile distribution mode.
Assign a Previously Created Profile Using a Distributor
To assign an existing profile to the FWSG (as you would do during a replacement), use the FWSG 
that has the profile, or a device in the mesh that contains the profile, to distribute that profile to the 
FWSG that requires it.  Perform the following steps:
1. Ensure that the FWSG or other mesh device with the profile is set for distribution (Refer to 
2. Start with the device powered off.  The process is performed during the start-up.
3. Power on the FWSG and ensure it is in the factory default state (Refer to steps 1 and 2 in the 
4. Bring the profile distributor within 20 feet of the FWSG.  
5. Wait until the FWSG blinks only a single red blink (ten seconds after startup).  
6. Use a magnet to activate either of the magnetic sensors.  The LED blinks a single red every 
half-second indicating that it is searching for a profile.
When the profile is successfully received from the distributor, the LEDs on the FWSG emit  green 
light for five seconds. If the profile is rejected,  the FWSG LEDs emit red light for five seconds.
Removing a Profile
To remove the profile from an FWSG, perform the following steps:
1. Start with the device powered off. The process is performed during the start-up.
2. Power on the FWSG using SLC power or external +24V.  This can be done either by attaching 
the FWSG to its mounting plate with the terminals already energized, or by connecting the 
SLC or external source wiring to a FWSG that is already installed in its mounting plate.
3. Verify the FWSG is in the profile modification state; if it is in the profile modification state, 
both the LEDs on the FWSG flash yellow (double blink) every second for ten seconds.
4. Activate both using magnetic sensors within ten seconds of starting up the FWSG (while the 
double yellow blink is active on the FWSG) or repeat step 1 (If you miss the ten second 
window, power down the FWSG and repeat steps 1 and 2).
The FWSG LEDs blink green every second for five seconds indicating that the profile is removed.
Create Mesh Network
Mesh formation forms a wireless communication mesh around the FWSG. The FWSG communi-
cates with all devices in range that have a common profile and establishes communication links 
with all the devices.  Once a device joins the mesh, it acts as a repeater for devices out of the range 
of the FWSG.  All devices must be in their final mounting locations prior to initiating the mesh for-
mation.  The mesh formation is initiated and terminated by the FWSG.
To form a mesh network, ensure that the FWSG is powered on and contains a profile (Refer to 2.7.3 
"LED Indications" for information on how the FWSG indicates its status).  Activate the mesh for-
mation magnet sensor on the FWSG with a magnet.