Honeywell International Inc. WFSSD Manuale Utente

Pagina di 74
PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013  
31
Operations
FWSG
7. Click Collapse Mesh.  The Collapse mesh network screen is displayed.
8. Click Yes. 
The network is collapsed and a confirmation is displayed as shown below:
Collapsing Mesh Network in the Panel
To collapse the mesh network using the NFS2-3030, refer to the "shutdown wireless" entry in the 
NFS2-3030 operations manual, part number LS10006-051NF-E.
2.7.7  Silence Network Command
The silence network command is a diagnostic function to turn off all radio communication from the 
wireless devices for the set amount of time.  All devices will retain the profile information but will 
be removed from the mesh.  The devices will not send or receive any wireless communication until 
the set time expires or the device is rebooted.  The mesh network can be reformed at the end of the 
silence period or after the device is restarted.    
CAUTION:
FIRE PROTECTION FROM WIRELESS DEVICES WILL BE LOST WHEN A 
SILENCE COMMAND IS ISSUED.
The mesh network can be silenced using the PC-based configuration tool or through the NFS2-
3030 panel.
Silencing Mesh Network Using PC Tools
To silence the mesh network using the PC-based configuration tool, perform the following steps:
1. Connect the W-USB dongle device to your computer.  For more information on USB dongle, 
2. Launch the PC Tools application.  Refer to Appendix B: "PC Tools" to know about launching 
the PC Tools application.
3. Go to Diagnostics step.
4. Select a Gateway from the Communicator pane.
5. Click View Mesh. The mesh is displayed.