Honeywell International Inc. WFSSM Manuale Utente

Pagina di 64
34
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
Wireless Devices
Configuration and Programming
3.
Change the address back to 0.
After the address wheel pattern is set, the LEDs in the device blink green five times followed by a single or double red blink confirming 
that the device has been reverted back to factory default condition.
Removing a Profile Using SWIFT Tools
To remove a profile in a device using SWIFT Tools:
1.
Connect the W-USB adapter to your computer. For more information on the USB adapter, refer to Section 5.
2.
Launch the SWIFT Tools application. Refer to Appendix A, “SWIFT Tools” for more information on launching the SWIFT Tools 
application.
3.
From the Home Screen, select the Site SurveyCreate Mesh Network, or Diagnostics function.
4.
Click Operations and select Set device to factory default
5.
Tamper and place powered-on devices that are to be reset in range of the W-USB.
6.
The Reset Devices screen appears, displaying the gateway and other devices that have a profile assigned. Click to select the desired 
device and click Reset Device to remove the profile.
The profile is removed and the device is reset to the factory default state.
TENS
8 9
10
11
12
13
14
15
0
1
2
3
4
5
6 7
ONES
8 9
0
1
2
3
4
5
6 7
Figure 3.6  Address Rotary Switches
SL
-se
ta
ddt
p
h.
w
m
f
NOTE: The above illustration depicts the rotary switches being set at address 35 (rotary switch on 'TENS' set at 3 and rotary switch on 
'ONES’ set at 5. Ensure that the code wheel address pattern is toggled within 1 minute of inserting the battery.