SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
Section 4: W-SYNC Wireless Synchronization Module
4.1  Description
The wireless synchronization module works with wireless AV base models WAV-RL, WAV-WL, WAV-CRL and WAV-CWL to provide 
audio and visual synchronization of a wireless notification appliance to a wired notification appliance. Synchronization is only available 
with notification appliances that use the System Sensor synchronization protocol. The W-SYNC also provides wireless control and mon-
itoring of a Notification Appliance Circuit (NAC) expander or power supply. It does not support the “whoop” pattern.
The wireless synchronization module operates from 24VDC power with supplemental battery support. A trouble will be generated at the 
panel if batteries are not installed or at a low battery level. Synchronization is not available during supplemental battery operation. For 
more information on the W-SYNC, refer to Document I56-6518 that ships with the product.
4.2  Wiring
The W-SYNC may be wired to compatible FACPs using an MDL3 Sync Module or the HPFF8/HPFF12 NAC Expanders. 
4.2.1  FACP
Wire the W-SYNC to the FACP as shown below. The synchronized output wiring must be contained in the common enclosure of mod-
ules or wired in conduit in enclosures mounted within 20 feet of each other  
ZONE 1
OUT
NAC 1
NAC 3
NAC 2
HORN
CONTOL
+
C
+
+
+
+
+
+
B+
B+
B+
A+
-
-
-
-
B-
B-
B-
A-
-
NC
-
-
-
-
+
+
ZONE 2
OUT
ZONE 1
IN
24VDC
NAC
SLAVE IN
ZONE 2
IN
SLAVE
OUT
SLAVE
IN
+
+
-
-
-
-
+
+
ZONE 1
OUT
HORN
CONTOL
+
+
-
-
-
-
+
+
ZONE 2
OUT
ZONE 1
IN
NAC
SLAVE IN
ZONE 2
IN
SLAVE
OUT
SLAVE
IN
+
+
-
-
-
-
+
+
UL-Listed power supply
Trouble Contacts
(if provided)
ELR*
ELR*
to next device or EOL
to next device or EOL
2 Class B (Style Y) Zones
1 Class A 
(Style Z) Zone
to next device
to next device
MDL3
MDL3
Slave
Slave
to next MDL3’s NAC 
SLAVE IN terminals
(4 MDL3 modules 
to next MDL3’s NAC 
SLAVE IN terminals
(4 MDL3 modules max.)
W-SYNC
synchronized output
Class B
(Style Y)
NACs
Class A
(Style Z)
NACs
*Note: If the power supply has trouble 
contacts to be monitored, install ELR 
supplied with W-SYNC on the power supply. 
If not, install ELR on W-SYNC.
Figure 4.1  W-SYNC Wiring to FACP