4. Software Interfaces 
 
-42- 
4.1.8 Scaling 
factors 
 
Current Range 
5 A 
20 A 
50 A 
100 A 
Active Energy Wh [Interval] 
64 16 6.4 3.2 
Active Energy Wh [Counter] 
8 2 0.8 
0.4 
Reactive Energy VARh [Interval] 
64 16 6.4 3.2 
Reactive Energy VARh [Counter] 
8 2 0.8 
0.4 
Apparent Energy VAh [Interval] 
64 16 6.4 3.2 
Apparent Energy VAh [Counter] 
8 2 0.8 
0.4 
Vrms 
25 25 25 25 
Irms 
1200 300  120  60 
Frequency 
16 16 16 16 
Active Energy Wh [Interval] 
64 16 6.4 3.2 
 
4.1.9 Energy 
counters 
Energy counters have the total consumed energy calculated by EMU. The reset 
command resets the energy counters, the recording interval counters, and the on-going 
interval accumulated values. 
The time-stamp of the energy counters is written into the register when the data is sent 
to EMG.   
Energy counters will count positive for energy consumed, negative for energy 
generated and pushed into the grid. Active, reactive, and apparent energy consumption 
values are stored as 32-bit values, thus using 2 Modbus registers.   
The lower register address contains the high word value (MSW: Most Significant Word) 
and the high register contains the low word value (LSW: Least Significant Word).   
  Registers: 0 to 23.   
16-bits 16-bits 
MSW LSW