4. Software Interfaces
-43-
4.1.10 Recording interval time (register 64)
Energy is integrated based on the recording time interval that is configurable.
The normal energy is calculated based on the period of five minutes with nominal
current and nominal input voltage.
The last completed interval values are stored in the register map.
The time-stamp is set in the time-stamp register at the end of the integration interval.
Registers: 32 to 43
4.1.11 Recording interval-based energy
The recording interval time is a configurable parameter that defines the recording
interval (minutes). It can have values for 5, 6, 10, 12, 15, 20, and 30.
The start of an interval is at the hour + n* interval.
When writing a value different from the ones listed to this parameter, it is discarded and
the EMU continues to use the previous set value.
Note that the EMG responds with an "ACK" to a write of an invalid value as it does not
check the contents of the message sent to the EMU.
4.1.12 Time stamp
The time stamp of the recording interval have the same format that uses three Modbus
registers.
Each of the registers is split into two parts as shown in the following table.
Register
High Byte
Low Byte
24 28
Minute
Second
25 29
Day
Hour
26 30
Year
Month
4.1.13 Frequency (register 27)
The Line Frequency is measured based on the phase of the power supply only (phase
1). The last value of the recording interval is stored in this register.