4. Software Interfaces 
 
-43- 
4.1.10  Recording interval time (register 64) 
Energy is integrated based on the recording time interval that is configurable. 
The normal energy is calculated based on the period of five minutes with nominal 
current and nominal input voltage. 
The last completed interval values are stored in the register map. 
The time-stamp is set in the time-stamp register at the end of the integration interval. 
  Registers: 32 to 43 
 
4.1.11  Recording interval-based energy 
The recording interval time is a configurable parameter that defines the recording 
interval (minutes). It can have values for 5, 6, 10, 12, 15, 20, and 30. 
The start of an interval is at the hour + n* interval.   
When writing a value different from the ones listed to this parameter, it is discarded and 
the EMU continues to use the previous set value. 
Note that the EMG responds with an "ACK" to a write of an invalid value as it does not 
check the contents of the message sent to the EMU. 
 
4.1.12 Time stamp 
The time stamp of the recording interval have the same format that uses three Modbus 
registers. 
Each of the registers is split into two parts as shown in the following table. 
Register 
High Byte 
Low Byte 
24 28 
Minute 
Second 
25 29 
Day 
Hour 
26 30 
Year 
Month 
 
4.1.13 Frequency (register 27) 
The Line Frequency is measured based on the phase of the power supply only (phase 
1). The last value of the recording interval is stored in this register.