5.8  PE test terminal 
 
It can happen that a dangerous voltage is applied to the PE wire or other accessible 
metal parts. This is a very dangerous situation since the PE wire and MPEs are 
considered to be earthed. An often reason for this fault is incorrect wiring (see examples 
below).  
When touching the TEST key in all functions that require mains supply the user 
automatically performs this test. 
 
Examples for application of PE test terminal  
 
L1
N
PE
Reversed phase and 
protection conductors!
T
 MOST DANGEROUS
SITUATION!
HE
 
Figure 5.33: Reversed L and PE conductors (application of plug commander) 
L1
N
Reversed phase and 
protection conductors!
MOST DANGEROUS
SITUATION!
PE
L
PE
N
L/L
1
N/L2
PE/L3
 
Figure 5.34: Reversed L and PE conductors (application of 3-wire test lead)